Louisiama ma ca.ooNo< smm P O W E R & L i G H T[ P o eox 6000
. NEW ORLE ANS LoutSIANA 70174
- 6504) 366 2345
=s ass April 24, 1984 W3K84-0928 Q-3-A35.07 hII$ @ [}!I]N U M p
}
Mr. John T. Collins APR ? 01984 Regional Administrator, Region IV U. S. Nuclear Regulatary Commission jd f) 611 Ryan Plaza Dri'e, Suite 1000 Arlington, Texas 76012
REFERENCE:
Telecon C. Hooper (LP&L) and J. Boardman (NRC Region IV) on March 22, 1984
Dear Mr. Collins:
SUBJECT:
Waterford SES Unit No. 3 Docket No. 50-382 Potentially Reportable Deficiency No. 161
" Emergency Diesel Generator 'A' Construction Damage" Final Report on March 22, 1984, an Emergency Diesel Generator (EDG) "A" overload condition was reported as PRD 161.
Further evaluation of the previously described condition indicates this condition is not considered reportable p'irsuant to 10CFR50.55(e).
EVALUATION During performance of OP-903-068, Surveillance Procedure, EDG "A" was overloaded to 5.8 eegawatts for a period of 1 to 2 minutes. The root cause of the overload condition was attributed to an improper governor setting. After recognizing the condition, LP&L immediately notified the vendor, Cooper Energy Services. On March 24, 1984, full load surveillance test was performed for one hour.
The test revented that no damage had occurred as a results of the overland condition. Based upon successful performance of EDG "A" during surveillance testing, this condition is not considered reportable.
Very truly yours, w,d
- El7 T. F. Gerrets Corporate Quality Assurance Manager TFG CNH:SSTG 0405070300 840424 PDR ADOCK 05000302 S
PDR g
ig
e Mr. John T. Collins April 24, 1984 W3K84-0928 Page 2 cc: Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Ccmmission Washington, D.C.
20555 (15 copies)
Director Office of Management Information and Program Control U. S. Nuclear Regulatory Commission Washington, D.C.
20555 Mr. E. L. Blake Shaw, Pittman, Potts & Trowbridge 1800 M Street. N.W.
Washington, D.C.
20036 Mr. W. M. Stevenson Monroe & Lemann 1424 Whitney Building New Oricans, Louisiana 70130 Mr. W. A. Cross 7910 Woodmont Avenue Suite 1200 Bethesda, Maryland 20814 L
.