Telecopy Message of Ao:On 710422,during Diesel Generator Load & Safeguard Sequence Test,Valves 826 A,B,C & D Failed to Open.Electrical Speed for Concentrated Boric Acid Storage Tank Level Instrumentation Moved to Bus Supplies
ML20084E666
Person / Time
Site: Ginna 
Issue date: 04/23/1971
From: Platt C
ROCHESTER GAS & ELECTRIC CORP.
To: Kirkman R
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20084E628 List:
References
NUDOCS 8304150239
Download: ML20084E666 (2)


Text

f-r 1

{

mM 4

  1. ele ram T

western union 737P EST APR 23 71 PB373 SYD433 SY RHA333 DF NL PDF ROCHESTER NY 23 f

R W KIRKMAN, DIRECTOR REGION 1 DIVN COMPLI ANCE USAEC l

970 BROAD ST NEWARK NJER THIS IS TO CONFIRM MY CONVERSATION AT 1632 THIS DATE WITH FLOYD 3

C ANTRELL IN REGARDS TO AN ABNORMAL OCCURANCE AT GINNA STATION THURSDAY NIGHT APRIL 22ND.1971 RGE MEN WERE DOING THE DIESEL

~

l GENERATOR LOAD AND SAFE GUARD SEQUENCE TEST THE UNIT Wes IN I

THE COLD SHf)TDOWN CONDITION WHEN THEY ACTUATED THE MANUEL, SAFETY INJECTION BUTTON THE. COST OF THE EXISTING ELECTRICAL HOOKUP j

WE LOST THE 1B INSTRUMENT BUS THE FEED FOR THE A CONCENTRATED BORIC ACID STORAGE TANK LEVEL INSTRUMENTATION WAS CONNECTED i

TO THIS BUS SO THE INSTRUMENTATION SHOWED LOW LEVEL IN THIS TANK AND THIS INDICATION WILL PREVENT VALVES 826A 826B 826C 8260 TO OPEN THIS WAS REVIEWED BY THE PORC COMMITTEE ON APRIL 23RD 1971 AND THE ELECTRICAL SPEED FOR THE A CONCENTRATED BORIC SF-1201 (R549)

I "~

W E8 Telegram lg mestern union i

I l

ACID STORAGE. TANK LEVEL INSTRUMENTATION WILL BE MOVED TO AN INSTRUMENT BUS SUPPLIES BY AN UNVERTER CHARLES E PLATT SUPERINTENDENT GINNA STATION ROCHESTER GAS AND ELECTRIC CORP 1632 22 1971 RGE 826A 826B F26C F260 231971

$N$ fl8g7/

%g

.M Xit 8304150239 710522 l-PDR ADOCK 05000244 S

PDR SF-1201 (R$49) i