Application for Amend to License DPR-50,consisting of Tech Spec Change Request 120 Re Engineered Safeguards Protection Sys Actuation Setpoints.Certificate of Svc Encl
ML20083N099
Person / Time
Site: Crane Constellation icon.png
Issue date: 01/21/1983
From: Hukill H
GENERAL PUBLIC UTILITIES CORP.
To: Stolz J
Office of Nuclear Reactor Regulation
Shared Package
ML20083N102 List:
References
5211-82-275, NUDOCS 8302010556
Download: ML20083N099 (4)


Text

.

GPU Nuclear Corporation G-U iuclear n','1e nce Bl Sluim o

48o Middletown, Pennsylvania 17057 717 944-7621 TELEX 84-2386 Writer"s Direct Dial Number:

January 21, 1983 5211-82-275 Offjec of Nuclear Reactor Regulation attn:

Jchn F. Stolz, Chief Jpcrating Beactors Branch No. 4

!!. S. Nuclear Regulatory Com.ission liashington, D.C.

20555

Dear Sir:

Three Mile Island Nuclear Statien. 'Jnit 1 (IMI-1)

Operating License No. DPR-50 Docket No. 50-289 Technical Spe $fication Change Pequest No. 120 Enclosed are three signed orig;nals and forty conforned copics of Technical Specification Change Request No. 120 requesting amendnent. to Appendin A nf Operating Licence Uo. DPR-50.

Also enclosed is on: Q ned copy of Certificate of Service for proposed Tc iniccI Specifica:1cn Change Request No. 120 to the chici executives of t'.c tomettip and county in which the !ccility is 1ccated.

Sincerely, D. nukill Directer, Oil-I 11H : CJ S 7j f lu c12:n.r a s :

1; Technical Specifica.lon Change Sequat No. 120 2)

Certificate of darvice for Iechnical Spee.ification Change T.equest No.

120 l

3)

Check No. 034965 g() /

cc:

im VI'e L

bC lO00*

8302010556 930121 gDRADOCK 05000289 PDR GPU Nuclear Corporation is a subsidiary of the General Public Utilities Corporation L

r m

+

METROPOLITAN EDISON COMPAhT JERSEY CENTRAL POWER & LIGHT COMPAhi i

AND PENNSYLVANIA ELECTRIC COMPAhi THREE MILE ISLAND NUCLEAR STATION, UNIT'l Operating License No. DPR-50 Docket No. 50-289 Technical Specification Change Request No. 120 This Technical Specification Change Request is submitted in support of Licensee's request to change Appendix A to Operating License No.

DPR-50 for Three Mile Island Nuclear Station, Unit 1.

As a part of this request, proposed replacement pages for Appendix A are also included.

GPU NUCLEAR CORPORATION I

By Director, TMI-l Sworn and subscribed to before me this 3 Law day of A......, 1982.

-e n

W.%, e __. -3 u...

Notary Public 3

f ak! A JfAN blRRY. N0!Akt FuPui:

'tETOWN BORD DAUPHIN Couh3 VfSSION EXPIRES JUNE 17.19e'

.nnsylvania Association of Notario

't I

UNITED STATES OF AMERICA NUCLEAR hEGULATORY COMMISSION IN THE MATTER OF DOCKET No. 50-289 LICENSE NO. DPR-50 GPU NUCLEAR CORPORATION This is to certify that a copy of Technical Specification Change Request No.120 to Appendix A of the Operating License for Three Mile Island Nuclear Station Unit 1, has, on the date given below, been filed with the U. S. Nuclear Regulatory Commission and been served on the chief executives of Londonderry Township, Dauphin County, Pennsylvania and Dauphin County, Pennsylvania by deposit in the United States mail, addressed as follows:

Mr. Jay H. Kopp, Chairman Mr. John E. Minnich, Chairman Board of Supervisors of Board of County Commissioners Londonderry Township of Dauphin County R.D. #1, Geyers Church Road Dauphin County Courthouse Middletown, PA 17057 Harrisburg, PA 17120 GPU NUCLEAR CORPORATION By Director, TMI-l Dated:

January 21, 1983

k TECHNICAL SPECIFICATION CHANGE REQUEST (TSCR) NO. 120 The Licensee herein requests that the attached changed pages replace the existing pages (3-37, 3-37a) of Appendix A of TMI-1 Technical Specifications.

I REASON FOR CHANGE REQUEST NO. 120 TS 3.5.3.1 footnotes (2) and (3) and Basis have been changed to raise the HPI and LPI allowable bypass setpoints for decreasing RCS pressure. The increased bypass setpoints allow more operator time to bypass HPI and LPI during normal plant cooldown.

This additional margin will compensate for instrument loop accuracies, bistable deadband settings and instrument drift, to preclude inadvertant actuation.

SAFE' Y ANALYSIS JUSTIFYING CHANGE The sncreased allowable HPI and LPI bypass setpoints preserve the necessary margin to bypass prior to alarm and actuation, which had been decreased due to the higher actuation setpoints required by Amendment No. 78.

Precluding inadvertant Engineered Safeguards Actuation System actuation prevents unwarranted cycling of the system components and does not adversely affect nuclear safety.

The actuation setpoints assumed in the safety analysis for Amendment No. 78 are not affected.

IMPLEMENTATION The proposed changes reflect existing plant conditions and Licensee, there-fore, requests that this License Amendment become effective immediately upon issuance.

LICENSE FEE (10 CFR Part 170.22)

The enclosed Technical Specification Change Request is submitted as a Class III Amendment with a subsequent fee to the Licensee of $4,000.00 enclosed.

_I_MPLEMENTATION TIME PERIOD It is requested that this Technical Specification Change Request be approved expeditiously in order that it may be implemented before initial criticality for Cycle 5.