ML20083J942

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 83-06 Re Nonconforming Matls Supplied by Tube-Line Corp.Matls Will Be Qualified by Demonstrating Suitability or Replaced W/Matls Mfg Per ASME Code Section Iii.Updated Rept Expected by 840423
ML20083J942
Person / Time
Site: Clinton 
Issue date: 12/23/1983
From: Hall D
ILLINOIS POWER CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-SSINS-6820 0982-L, 982-L, IEB-83-06, IEB-83-6, NUDOCS 8401050527
Download: ML20083J942 (5)


Text

_ _ _ _ _ _ _

J. G. Keppler 2

December 23, 1983 B.

BA Purchase Orders are now accompanied by a statement that materials shall not be supplied which have been procurred from either Ray Miller, Inc., (IE Bulletin 83-07) or Tube-Line Corporation.

3.

All Tube-Line supplied materials will be either qualified by demonstrating that such materials are suitable for intended service, or replaced with materials which have been manufactured in compliance with ASME Code Section III and applicable procurement specification requirements.

4.

The plan for resolution of IE Bulletin 83-06 includes, but is not limited to the following:

A.

Identify materials supplied by T-L.

B.

Review site procurement and installation documentation to locate all T-L supplied materials.

C.

Write Nonconformance Reports (NCRs) on materials supplied, addressing location and installation condition (i.e., in Warehouse, in process of installation, skid mounted, installed, etc.).

D.

Disposition NCRs (replace or qualify to demonstrate suitability for intended service).

Illinois Power will provide your office with an update on resolution of IE Bulletin 83-06 by April 23, 1984.

If there are further questions on this matter, please notify Illinois Power Company.

I hereby affirm that the information in this letter is correct to the best of my knowledge.

l Sincerely, i

l D. P. Hall Vice President RA/cbs Attachment cc:

US NRC, Document Control Desk, Washington, D.C.

G. A. Harrison, NRC Clinton Licensing Project Manager NRC Resident Office Illinois Dept. of Nuclear Safety 8401050527 831223

~

PDR ADDCK 05000461 G

PDR

.m

. Safety Material Matarial Ralstad

- Quantity Description Type HT f/ Code Yes/No Installed NCR f/ Disp.

P. O. #

Status 1.

8" L.R.

SA 403 AAEJ Yes BA C33077 Cut into 2 ea. 45' El's 90* E1.

CR WP Researching Sch/40 304 W

'I 2.

6 3" S.R.

SA 403 AADI Yes No 10121 Return C34395 In WHSE #2 for return 90' EL CR WP to Vendor

'l Sch/40 304 W t

3.

4 4" STD SA 234 EUYC Yes No 10121 Return C38249 In WHSE #2 for return.

r Cap WPB to Vendor Auth IST #7566 1

Sch/40 4.

2 8" 45' SA 234 EIOC Yes No 10121 Return C36469 PIL Hold for Ret. to I

L. R. ELs WPB to vendor Vendor. Auth MRT #7564 l

5.

12 4" XH SA 234 E22C Yes No 10121 Retura C38018 In WHSE #2 for Ret. to CAPS Sch/80 WPB to vendor Vendor. MRT #7565 6.

3 4" Std SA 234 EUTC Yes No 10121 Return C38249 PW-4 Hold for Ret. to CAP Sch/40 WPB to vendor vendor leT #7566 1

7.

I 12" 150f SA 182 ABXA Yes Yes 10121 Return C37770 To be renoved and returned j

R.F. Blind (SF Systen) to vendor to vendor I

Flange (Main Stean)

I

(

l 8

I 11" 150f SA 182 ABAA Yes Yes 10/21 Return C37770 To be removed and returned l

WN FLC (SF Systen) to vendor to vendor

}'

Sch/40 (Main Stean)

L j

9.

18 2" 300f A 105 272425 DHN Yes BA N/A part of D. C. Air Start Piping

{

'R.F. SW Researching DC Sets Std. Flange i

10.

64 2" 300# R.F. SW A-105 E1423 DQO Yes BA N/A D.C. Air Start Piping;

[

i Std Flange Researching part of D.C. Purchase Order 4

(

5 i

1 5

t i

a s

?

i

Safsty Material Material

Related Quantity Description Type HT f/ Code Yes/No Installed NCR #/ Disp.

P. O. #

Status II.

30 2" 300f R.F.

A-105 272425A DJY Yes BA N/A D.C. Air Start piping; SW Std Flange A-105 Researching Part of D.C. Purchase Order 12.

6 6" Std SR El SA-234 Wpb XRS (DRS)

Yes BA RA investigating location Researching to determine status 13.

22 14" OD 150#

SA-181 CR II 677206 Yes BA C06882 BA itvestigating location WM FF Flange Researching to determine status 14.

I 16" 90* EL SA-234 WPB CER 319113 Yes BA C06882

.EA investigating location 3/8" wall Researching to determine status thk.

15.

4 16" 90* El SA-234 WPB CER 319113 Yes BA C06882 RA investigating location 3/8" vall Researching to determine status thk.

16.

2 8" 150# WN FF A-105 85890 Yes BA C06882 RA investigating loct, tion FLC Sch/40 Researching to determine status 17.

15 6" 150f WN FF SA-105 COP 40575 Yes BA CO6882 BA researching location to Fig Sch/40 Researching determine status 18.

4 18" 45* EL SA-234 WPB CIM 154568 Yes BA CO6882 BA researching location to Researching determine status 19.

2 8" 150f WN RF SA-181 CF II CCS 83925 Yes BA C06882 BA Researching location to F1g Researching determine status 20.

12 18" SYP LR A-234 CIM 1545568 Yes BA C06882 BA researching location to 90* EL Researching determine status 21, 2

14" STD SR A-234 C0J 134587 Yes BA C06882 BA researching location to 90* EL 3/8" researching determine status weld thk.

.. = - --. --

Stfsty

-Matsrial Materini Reltttd Quantity Description Type HT f/ Code Yes/No Installed NCR f/ Disp.

P. O. f Status 22.

4' 18" SRO SR A-234 OPH 143167' Ten BA C06882 BA researching location to 90* FL 318" researching determine status vall thk 23.

4 14"x14"d" A-234

'CLE 250843 Yes BA C06882 BA researching location to STD Red Tee Researching determine status 24.

10 14" STD 45' A-234 CQG 131139 Yes-BA C06882 BA investigating location EL Researching to determine status 25.

1 24" x 16" ECC SA-234 WPB ERIK Yes BA C39025 BA investigating location Red Tee Researching to determine status 26.

16 34" 90' EL SA-403 AAWY Yes BA C25176 BA investigating location Sch/10 LR researching to determine status 27.

12 2" 60# R.F.

Returned to vendor part of Sw F1g investigation 21-83-01 ref Itr WJR 61-83 I

s s

k 4

I s

I s

?

.