' hl)/ 0

?

Donald A. Wells Macagar-Ouakty Assurance 013) 2376057 2000 Secord Avenue D

December 22, 1983 g3 h 3 Q n 48226 EF2-66489 Mr. James G. Keppler, Regional Administrator Region III U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Subj ect: Interim Report of 10CFR50.55(c) Item on Undersized Battery Cables (#61)

Dear !!r. Keppler:

This interim report involving undersized battery cables has been prepared to provide the current status of this problem.

~ This item was originally reported to Mr. J. Neisler of NRC Region III by Detroit Edison's Mr. J. D. Ryan, Quality Assurance Engineer -

Project Quality Assurance on March 12, 1983.

During the course of a review of the D.C. system for battery load curve data, it was discovered that some cables were inadequately sized. The circuits were primarily associated with motor operated valves and switch gear, where long lengths of cable had been used.

Approximately thirty-five (35) circuits were affected.

~

Sixty-four (64) Design Change Notices (DCNs) have been issued to make the necessary cable changes. Of these, only three (3) DCNs remain open and work is continuing.

Another report on this item, either interim or final, will be sent when further information is available.

If you have questions con-cerning this matter, please contact Mr. G. M. Trahey, Assistant Director - Project Quality Assurance.

Very truly yours, gRADOCKO1050405 831223 05000341 g

PDR 1

e DEC 3 0 W

.~-

Mr. James G. Keppler, Regional Administrator December 22, 1983 EF2-66489 Page 2 cc:

Mr. Richard DeYoung, Director Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Mr. Paul Byron, Senior Resident Inspector U. S. Nuclear Regulatory Commission 6450 North Dixie Highway Newport, Michigan 48166