$VL
~7 pT A
2NRC-3-iO5 (412) 787 - 5141 Telecopy 2) 8 -
December 29, 1983 Nuclear Construction Division Rc5inson Plaza. Building 2, Suite 210 Pittsburgh, PA 15205 United States Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:
Mr. Harold R. Denton Of fice of Nuclear Reactor Regulation
SUBJECT:
Beaver Valley Power Station - Unit No. 2 Docket No. 50-412 Preservice Inspection Program Centlemen:
At t ach ed is a de sc ri p t io n of the Pr es e rv ice Ins pe ct ion Program initial plan.
NRC Ques tion 250.1 cont ained in the enclosure to Mr. G. W. Knighton's letter to Mr.
E.
J.
Wooleve r dated S ept embe r 19, 19 83, req ue s t ed this i nfo rma t ion for development of the Safety Evaluat ion Report.
Our res po ns e s ubm i t ted in FS AR Amendment 4 on Decembe r 5, 1983, inc luded a commitment to supply this inf o rma t io n.
DUQUESNE LIGHT COMPANY l
By
/
E(/ J.~ Woolever Vice President JJS/wjs At t achment COMMONWEALTH OF PENNSYLVANIA )
)
SS:
COUNTY OF ALLEGHENY
)
On this
_2////
day of bluir//C
, j //J be fo re me,
a Notary Pub lic in and fo r sa id Commonwealth and County, pe rsonal ly appeared E. J. Woolever, who being duly sworn, deposed and said that (1) he is Vice President of Duquesne Light, (2) he is duly authorized to execute and file the fo regoing S ubmi t t al on behalf of sa id Com pa ny, ani (3) the s t at eme nt s set fo rth in the S ubmi t,t al are true and correct to the bes t of his knowledge.
gj O
,hy;[
ud k Ebe
\\
\\
Not ary Pub lic 8401040169 031229 PDR ADOCK 05000412 Q
PDR ANITA ELAINE REITER. NOTARY PUGLIC ROBINSON TOWNSHP, ALLEGH34Y COUNTY MY COMM!SSION EXPIRES OCTOBER 20.1:36
'o The Freservice Inspection Program initial plan description is as follows :
1.
Codes ASME Section XI 1980 Edition up to and including Winter 1980 Addenda, Regulatory Guides 1.26, 1.143, and 1.150.
Code of Federal Regulations 10CFR50.55a(g) 2.
The program will include, but not be limited to, subsect ions IWA, IWB,
IWC, I WD, IWF, IWP, IWV, and Mandatory Appendices.
Relief requests would be submitted to the commission once it becomes known where Section XI examinat ion requirement s cannot be met.
3.
Following the preservice examination inspections, a complete list will be availab le for all items examined and relief requests.
4.
The Inspection Program plan will include Isometric sketches identifying the welds and support s or bolted connections subject to examination in each piping system.
Areas To Be Examined:
a.
Reactor Vessel b.
Pressurizer c.
Piping Class 1, 2, and 3 e.
Reactor Coolant Pumps, Residual Heat Removal Pumps, Charging Pumps,
~
Recirculation Spray Pumps, Low Head Safety Injection Pumps, and other Class 2 and 3 Pumps f.
Valves Class 1, 2, and 3 g.
Excess Letdown Heat Exchanger h.
Residual Heac Exchangers
- i. Seal Water Heat Exchanger
- j. Non-Regenerative Letdown Heat Exchanger k.
Regenerat ive Heat Fxchanger 1.
Volume Control Tank m.
Accumulator Tanks n.
Seal Water Injection Filters o.
Reactor Coolant Filter p.
Seal Water Return Filter q.
Recirculat ion Heat Exchanger
- _ - _. _ _.