Amends 163 & 162 to Licenses DPR-32 & DPR-37,respectively, Providing Alternative to Impractical Requirement of Hourly Containment Entries by Fire Watch to Compensate for Inoperable Fire/Smoke Detector in Containment
ML20083F306
Person / Time
Site: Surry  
Issue date: 09/26/1991
From: Berkow H
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20083F307 List:
References
NUDOCS 9110040192
Download: ML20083F306 (7)


Text

_ - _ -

~ ~..

Y jo, UNITED STATES

,a NUCLEAR REGULATORY COMMISSION 5

W ASHING TON. D. C. 205$b I

%...+/

VIRGINTA ELECTRIC AND POWER COMPANY DOCKET NO. 50-280 SURRY POWER STATION, UNIT NO. 1 AMENDMENT TO TACILITY OPERATING LICENSE Amendment No. 163-License No. DPR-32 1.-

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Virginia Electric and Power Company (the licensee) dated August 24, 1990, es supplemented August 28, 1991, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter 1; B.

The facility wi11 ' operate in conformity with the application.

the provisions of the Act, and the rules and regulations of the Comission; C.-

Thereisreasonableassurance(1)thattheactivitiesauthorized by-this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities wi'l be conducted in compliance witn' the Comission's regulations;

.D.

The issuance-of this amendment will not be inimical to the common

' defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part

51. of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment'to this license l

amendment, and paragraph 3.B of Facility Operating License

'No. DPR-32 is hereby amended to read as follows:

L l

NodOUMOCK05000200 192 9109n6 P

Phn l

r.

~.

t (B) Technical-Specifications 1

-The Technical: Specifications contained in Appendix A, as revised through~ Amendment No.163, are hereby incorporated in tha license.

The licensee shall operata the facility in accordance with the Technical Specifications.

3.-

This license: amendment is effective as of the date of its issuance.

FOR.THE NUCLEAR REGULATORY COMMISSION RTd4/

4

.ted Herbert N. Berkow -Director

{

Project Directorate 11-2 Division of Reactor Projects - 1/11

-Office of Nuclear Reactor Regulation-Atta chment:--

Changes to the Technical-

Specifications Date-of-Issuance: September 26, 1991 t-

~'

I I

l.

(

  • /#*%

o UNITED STATES F,

NUCLEAR REGULATORY COMMISSION h

.j WASHINGTON, D. C 20555 a

l VIRGINIA ELECTRIC AND POWER COMPANY DOCKET NO. 50-281 SURRY POWER STATION, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Am ndment No.162 License No. DPR-37 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Virginia Electric and Power Company (the licensee) dated August 24, 1990, as supplemented August 28, 1991, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Cornission; C.

There is reasonable assurance (i) that the activities tuthorized by this amendment can be conducted without endangering (Se-health and safety of the peblic, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to tha commo-defense and security or to the health and safety of the public; and E.

The issuance of this amendnient is in accorsance with 10 CFR Part 51 of the Commission's regulttions and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B of Facility Operating License No. DPR-37 is hereby amended to read as follows:

1 1

. (B) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment ho.162, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment it effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION ekQ J~

)

i W Herbert N. Berkow, Director 4

Project Directorate 11-2 Division of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: September 26, 1991

ATTACHMERT TO LICENSE AMEN 0 MENT AMENDMENT NO.

163 FACILITY OPERATING LICENSE NO. DPR-32 AMENDMENT NO.

162 FACILITY OPERATING L_ICENSE NO DPR-37 DOCKET NOS. 50-280 AND 50-281 Revise Appendix A as follows:

Remove Pages Insert Pages TS 3.21-1 TS 3.21-3 TS 3.21-5 TS 3.21-5

TS 3.213 9.

Yard Fire Hydrant and Hydrant Hose Houses - as listed in Table 3.213 shall be operable when equipment or structures served by the hydrant or hose house is required to be operable, 10.

Fire Barrier Penetration Fire Seals protecting safety related areas shall be functional.

B.

Specifications 3.21.A.1 through 3.21.A.10 may be_ modified as described below provided immediate attention is directed to making repairs.

1.

_With the number of operable fire detection instruments less than required by Specification 3.21.A.1, within one hour establish a fire watch patrol to inspect the zone with the inoperable instruments at least once per hour, unless the inoperable instrument (s) is (are) in containment, then inspect the containment at ieast once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or monitor the containment air temperature at least once per hour with the permanently installed RTDs.

2.'

Specification 3.21.A.2 (Fire Water Suppression System) a.--

With less than required ~ equipment:

-(1) ' Restore the inoperable equipment.to an operable status, within 7 days, or provide an atternate means to accomplish the Inoperable function,-

. b.

With no Fire Suppression Water System, establish a backup Fire

. Suppression Water System within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

-3.

Specification 3.21.A.3 (Spray and Sprinkler Systems) - with a sprinkler system inoperable establish a continuous fire watch, with backup fire suppression equipment, for the unprotected areas within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

I i

Amendment Nos. 163 and 162

.7

f s

[

TS 3.215 BASf3 Fire Delection Instrumentation Operability of the fire detection instrumentailon ensures that adequate warning capability is available for the prompt detection of fires. This capability is required in older to detect and locate fires in their early stages. Prompt detection of fires will reduce the potential for damage to safety related equipment and is an integral element in the overall facility fire protection program, in the event that a portion of the fire detection instrumentation is inoperable, the establishment of frequent fire patrols in the affected areas or an alternate method of fire detection (permanently installed RTDs)in -

the containment is required to provide detection capability until the inoperable instrumentation is returried to service.

Fire Sucoression Systems The operability of the fire suppression systems ensures that adequate fire sup;.ression capability is available to_ confine and extinguish fires occurring in any portion of the facility where safety related equipment is located. The fire suppression system consists of the water system, spray and/or sprinklers, CO2, Halon, and fire hose stations. The collective capability of the fire suppression systems is adeqvate to minimize potertial damage to safety related equipment and is a major element in the facility fire protection program in the event that the fire suppression water systems are inoperable, immediate corrective measures must be taken since this system provides the major fire suppression capability of the plant.

Amendment Nas. 163 and 162

.