p e

Georgia Power Company 333 Piedmont Avenue Atlanta, Georg:a 30308 Telephone 404 526J726 Ma.!'ng Addrew Post Off.ce Box 4545 Atlanta, Georgia 30302 h

m 22 all : 08 Georgia Power O

D. O. Foster the southern eectrc systern Vice Pres.aert and General Manager VogtW Pro;ett December 19, 1983 United States Nuclear Regulatory Commission File: X78G03-M41 Office of Inspection and Enforcement Log:

GN-294 l

Region II - Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Reference:

Vogtle Electric Generating Plant - Units 1 and 2 50-424, 50-425; Embed Plate Base Metal Failure l

l Attention: Mr. James P. O'Reilly l

Gentlemen:

l Georgia Power Company has been conducting an investigation into this i

event as previously outlined in our letter GN-240 dated 7-11-83. The field inspection program; however, was modified to include weld size as an additional variable. Georgia Power Company has identified a total of four hundred and forty-seven (447) installed embed plate supports. Of these, fifty-four (54) were randomly selected for visual inspections and magnetic particle testing on all flare bevel welds made to the embed plate or sur-face mounted plates. No lamellar tearin the inspection of these fifty-four (54) g indications were identified in samples.

Georgia Power Company intends to use the results of the inspection of the fifty-four (54) assemblies in its evaluation of this concern for reportability pursuant to the requirements of 10 CFR 50.55(e) and 10 CFR 21.

Georgia Power Company expects to submit a final report on the results of this evaluation by February 17, 1984.

This response contains no proprietary information and may be placed in the NRC Public Document Room upon receipt.

7 l

./

Y0st) y,'&

. '0. Fos r D0F/REF/cc xc:

U. S. Regulatory Commission Document Control Desk twridI AL COW.

Washington, D. C.

20555 gp xc:

R. J. Kelly D. E. Dutton J. A. Bailey L. T. Gucwa R. E. Conway W. F. Sanders

0. Batum M. Malcom G. F. Head R. H. Pinson H. H. Gregory, III G. Bockhold J. T. Beckham, Jr.

B. M. Guthrie C. W. Hayes P. D. Rice D. N. MacLemore R. A. Thomas E. D. Groover J. L. Vota 8312280466 831219 PDR ADOCK 05000424 I [h s

pon ij v

_ _ _ _ _ _ _ _ _ _