7590-01 UNITED STATES OF AMERICA NUCLEAR REGULAT0rY C0t?il,55,1,0N In tne !!atter of
)
)
POWER AUTHORITY OF THE
)
Docket No. 50-333 STATE OF tiEW YORK
)
)
(Jarres A. Fit: Patrick
)
tiuclearPowerPlant)
)
EXEPPTION 1.
The Power Authority of the State of t;ew York (PASt4Y/ licensee) is the holder of Facility Operating License No. DPR-59, which authorizes operation of the James A. FitzPatt ick tiuclear Power Plant (the f acility).
The license provides, among other things, that the f acility is subject to all rules, regul3tions and Orders of the Nuclear Regulatory Commission (the Commission) now or hereafter in effect.
The f acility is a boiling water reactor located at the licensee's site in Oswego County, t;ew York.
11.
On November 19, 1980, the Commission published a revised Section 50.48 and a new Appendix R to 10 CFR Part 50 regarding fire protection features of ruclear power plants (45 FR 76602). The revised Section 50.48 and Appendix R became effective on February 17,19E1.
9io9250257 h0 h 33 0
PDR ADOCK ppa F
m. _ _ - _
9 2
Section ll!,G of Appendix R to 10 CFR Part 50, requires that where cables or equipment of redundant trains. of systems necessary to achieve and maintain hot shutdown conditions are located within the same fire area outside of primary containment, one of the following means of ensuring that one of-the redundant. trains is free of fire damage shall be provided:
a.
Separation of cables and equipment and associated non-safety circuits of. redundant trains by_a fire barrier having a 3-hour rating.
Structural' steel forming a part of or supporting such fire barriers shall be protected to provide fire resistance equivalent to that required of the barrier; b,
Separation of cables and equipment and associated non-safety circuits of redundant trains by a horizontal distance of more than 20 feet with no intervening combustible or fire hazards, in addition, fire detectors and an ' automatic fire suppression system shall be installed in the fire area; ur l
c.
Enclosure of cable and equipment and associated non-safety circuits of one redundant train in a fire barrier having a 1-hour rating. -In addition, fire detectors and an automatic fire suppression system l
shall be installed in the fire area, t
l If these conditions are not satisfied, Section !!!,G,3 of Appendix R to L CFR Part 50 requires alternative shutdown capability independent of the fire area of concern.
Furthermore, this section_ requires that fire detection and a
(
- fixed' fire suppression system be provided in areas, rooms, or zones for which alternate shutdown capability is provided, i
m
=. '
l 3
g By letter dated July 31, 1991, and supplemented by letter dated August 6, 1991,. the licensee requested an exemption f rom the requirerrents of 10 CFR Part 50, Appendix R Section 111.G.3.
Specifically, the requested exemption pertains to the requirement to have a fixed suppression system in the Battery Room Corridor.
The Commission pay grant exemptions from the require;r.ents of the regulations which, pursuant to 10 CFR 50.12(a), are:
(1) authorized by law and will not
.cndanger life or property or-common defense and security and are otherwise in the public interest, and (2) present special circumstances.
Section50.12(a)(2)(ii) of 10 CFR-Part 50 indicates that special circumstances exist when application of the regulation in the particular circumstances would not serve the underlying purpose of the rule or is not necessary to achieve the underlying purpose of the rule.
Ill.
The proposed exemption is needed as the result of the licensee's investigation of deficiencies identified during a review of the FitzPatrick fire protection program.
The licensee recently determined that redundant cables for safe shutdown systems are located in the Battery Room Corridor fire Zone BR-5.
Alternative shutdown capability -is required for this area as a result of possible loss of Divisions "A" and-"B" cabling due to a fire in the area. Modifications previously implemented in Fire Zone BR-4 to ensure alternative shutdown j
capability for-a fire in the main control room also ensure alternative 1
l shutdown capability for a fire in Fire Zone BR-5.
This alternative shutdown i
l..
t_
. capability is provided by the provisien of Division "B" dc power to the remote stutdown panels via distribution panel 71 DC-Ed (Fire Zone EG-6). Automatic fire detection is pt evided for the Cattery Rocn Corridor; hcwever, fixed fire suppressico system capability is rot.
As a result, the Eattery Poom Corridor is not in conpliance with Section Ill.G.3 of Appendix R to 10 CFR part 50.
The Pattery Room Corridor has low con.bustible loading consistirg prfmarily of cable insulation. Any fire in the insulation would be expected to develop sitwly. Furthermore, this corridor has an equivalent fire severity of less than one hour. Autcmatic detection consisting of ceiling mounted ionization detectors is provided in this corridor.
Potential fires in the Eattery Room Corridor would involve prinarily cable insulation located in trays rear ceiling level or in vertical risers along the south wall.
Fires of this nature would be detected in the incipient stage, with alarm nntification in the continucusly-manned main control room. Alarm notification would result in prompt dispatch of the fire brigade for rapid initiation of manual fire i
fighting activities, portable extirguishers and manuai hose stations are provided in the Battery Room Corridor and adjacent areas to assist in this fire fighting effort.
Reasonable assurance is provided that manual fire fighting activities would result in prompt extinguishment of postulated fires.
Since alternate shutdown capability is provided independent of the fire crea of concern, any fire that was to occur in the Battery Room Corridor would not affect the ability of the plant to achieve and maintain safe shutdown.
we
5.
Based on the above evaluation, the staff concluded that application of the regulation.in this particular circurstance is not necessary to_ achieve the underlying purpose of Appendix R to 10 CFR Part 50.
The current level of fire protection'in the Battery Corridor provides an equivalent level of fire safety as that required by 10 CFR part 50, Appendix R, Section Ill.G.3, and does not adversely affect plant safety.
Therefore,-an exemption to the requirements of Section !!!.G.3 of
-Appendix R to 10_CFR Part 50 in relation to fixed fire suppression in the Battery Ecom Corridor should be granted.
IV.
Accordingly, the Commission has determined, pursuant to 10 CFR 50.1?(a),
that (1) the exemption as described in Section Ill. is authorized by law and will not. endanger life or property.or common defense and security and is otherwise inithe public interest, and (2) in this case, special circumstances are present in that application of_the regulation is not necessary to-achieve the u~nderlying purpose of-10 CFR part 50, Appendix R.
- Accordingly, the Commission-hereby grants the exemption from the requirements of Section !!!.G.3 of Appendix R to 10 CFR Part 50-regarding a fixed fire suppression system in the Battery Room Corridor.
- = - ~ -
f.
6-Pursuant to 10 CFR 51.3?, the Conmission has deterrained that the granting (f this owption would have no significant effect on the quality of the human er:v ir u r ent (EE FP 42363, August 27,1991).
This Eser.ption is effective upon issuance.
F0P THE tiUCLEt, R
'LATORY COMf115510tl h
.{
' a(ita(, Direc
(
n#.
r Division of Reactor Pr 4> cts - 1/11 Office of t;uclear Reactor Regulation Cated at PecLville, Maryland, this 18tn cay of September 1991 I-l l
l 7
V:.
. r,.
1 Pursuant to 10 CFR 51.32, the Connission has determined that the granting of this exemption would have no significant effect on the quality of the human environment (50 TR 42363, August 27,1991).
This Exemption is effective upon issuance.
FOR THE NUCLEAR REGULATORY COMMISSION ORIGtR% SIGic BYs Steven A. Varga, Director Division of Reactor Projects - I/11 Office of fluclear Reactor Regulation Dated at Rockville, Maryland, this 18th day of Septembe.r 1991
- See previou.; concurrence g_.
. ).g_ _.....
_...___....g.....~~'
- PD1 1:0.
i
,s.....
HAME
- CVogan cd
- BMcCabe:avi p :*CMcCracken
- RAO) [4]
bkk t h 5)h1 fkfhfh5
!bh)bbfh[
!bhfbS)h[
Ifff91 DTt-':hbhr~~]1{.....:~ ~ hk Pl~7i"..~..~.'......~. T * " "
HAME
- JC31vo 4
g
... {7, #
DATE
- 9/7/91
/91 1TTltlhE kttDkb tDPT-" ~ ~ ~ ~ ~~ ~'" ~ ~~" ~~~~ ~ ~ ~ ~ ~ ~ ~ ~~ ~'~~~
~
Document Name:
FITZ EXEMPT 81184
4 Mr. Ralph E. Beedle
-?-
September 18, 1991 required by 10 CFR Part 50, Appendix R, Section 111,0.3, in your letter dated August 16, 1991, you concitted to install a fixed fire suppression systetr in this area prior ta startup from the 1992 refueling outage. This commitment was nade as pari of 1he fire protection progt am iaprover,ent ef fort s current'y being conducted at the FitzPatrick Plant.
Sincerel O RIG M AL ONO Me P.cbert A. Capra, Director Project Directorate 1.1 Division of Reactor Projects.1/11 Office of Nuclear Reactor Regulation
Enclosure:
Exemption cc w/ enclosure:
See next page Distribution:
fiocket File Enc & Local PORs 001 1 Reading Tf'urley/FMiraglia, 1?/G/18 JFartlow, 12/G/18 CRossi,11/E/4 SVarga JCalvo CVogan SMcCabe PAcapra CAnderson, P.!
PArchitzel, 8/0/1 PMadden, 8/D/1 DHaverlamp, RI OGC EJordan, MN0B/3701 Chill (4)
ACRS (10)
GPA/PA OC/LFMB KB roc kria n, 17/G/21 CCowtill, RI CMcCracken, S/D/11
- See previous concurrence DTt' ~ iPbT-T:lW ~ ' ' ~ ~ ~ ': Pbr-lilF ' ' ' ' i 3PLPP ' ~ ~ ~ ~ ~ ~ ~ i DC ~ ' ' ~ ~ ~' ~~ i tbT-T:~li
......:...._......:._....._......j*...........:....._......_:.jk h.,,
- CVogan
- PMcCabe:ay1 %
CFcCracken a
NAME
- y
.....:. o..
DATE
- %/O/91
- ']/IS/91
- 09/03/91
- 09/0E/91
.f.//f/91
. _.(..
p..
......:....... 3.li b. p g.-......:.. _
/
NAME
- JCalvo T i-a
...._ :........___....:7 f//f/91
/91 DATE Offill/F EECDRii~ PY''''~~~~~~~~
'~~~ ~ ^
~~ ~ ' ' " ~ ~ ~ ~ ~ ~ " ~ ~
~
Document tlene-FIT 7 DEPPl 81184
. _ - _ _ _ _ _ _ _ _