e a-A Gentgia Pom comr3ny 333 Piedmont Avenue Avanta Georrra 30308 T&mcoe 40i 5?6-7893

{J q y p p "' J,' t y ~[

,e u.

9 Mamng Address Fost Oftcc Box 4545

_ At:ania. Georwa 30302 33 DEC 13 P 4 22 G. F. Head sener vice erescent NED-83-584 ev.w nonerav,n November 21, 1983 U. S. Nuclear Regulatory Comnission REFEREbCE:

Office of Inspection and Enforcement RII: JPO Region II - Suite 2900 50-321/50-366 101 Marietta Street, N4 I&E Bulletin Atlanta, Georgia ' 30303 83-06 ATTENPION: Mr. James P. O'Reilly GENTLDEN:

Georgia Power Conpany submits the following information in response to IEB 83-06, concerning nonconforming materials supplied by Tube-Line Corporation.

In response to Action Item 1 of the reference bulletin, we have reviewed the lists of purchasing and receiving companies given in Attachments 2 and 3 Ittis review disclosed - that Tube-Line materials have been to the bulletin.

furnished for use at Plant Hatch.

Action Item 2.a.

requested, for operating plants, a list of Tube-Line materials which' are not yet installed in safety-related systems.

The following response is provided:

Consolidated Pipe and Supply provided the following materials:

( 1) 8"x16" stainless steel reducer

( 1) 10"x18" stainless steel reducer

.C @itol Pipe and Steel provided the following materials:

( 1) Piece 6"x3" 540 LR 90 degree elbow SA234 WPB heat code #EGX (12) Pieces 4" 540 CAP SA234 WPB heat code #EUYC IUB Imorporated provided the following materials:

( 4) Pieces 10" SCH 10 LR 90 degree elbow WP304-W Action Item 2.a.

further requested identification of safety-related systems in which these materials would be installed. None of the materials listed above will be used in safety-related systems.

All items have been placed under a quality control hold' and will be evaluated for use in nonsafety-related systems only.

Action Items 2.b.

and 2.c.

require no response since no Tube-Line materials will be installed in safety-related systems.

831'2200395 831121

%(k [g PDR ADOCK 05000321 1

(

G PM

+ _

,_c.

V

- Q-Georgia Power n U. S. Ntaclear Regulatory Conmission

-Office of-Inspection and Enforcement Novenber 21, 1983 Page 2 Action Item 3.a.

requested a list of Tube-Line materials that had previously been installed in safety-related systens.

One such item was provided by Capitol Pipe and Steel and installed in the Plant Service Water

- (PSW). System - in the strainer backwash system located at the intake structure.. This was a 6"x3" 540 IF 90 degree elbow SA234 heat code IEGX.

Pursuant to Action. Item 3.b., an evaluation was performed to determine the suitability of installed Tube-Line materials for intended service.

The result of our evaluation was, for this particular installation in the PSW strainer backwash system, that no safety or e.perability problems would be posed by allowing the material to rerain in place.

This coupletes our response to IEB 83-06. Please contact this office if further information is required.

G. F. Head states that he is Vice President of Georgia Power Conpany and is i

authorized to execute this oath on behalf of Georgia Power Conpany, and that to the best of his knowledge and belief the facts set forth in this letter are true.

GE0fGIA PChER CXNPANY By:

k. ?, /

[

G. F. Head Sworn to ubscribed before me this 21st day of November, 1983.

Y-'

a o.-

l

/

T No@

lic E [fb Notary Public, Geor$, State at h Ny Commiss:on Expires July 16,1953 Enclosure i