Text
. _ _ _ _ _ _ _ - - - _
s-,r.d Log # TXX-91343 L
Fi1e # 10110 Z
903.8 Ref.
- 10CFR50.55(e) 7UELECTRIC S ptember 17, 1991 Williarn J. C ahill. Jr.
Execussw I'sce />rseJent U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.
20555
SUBJECT:
C0 HANCE PEAK STEAH ELECTRIC STATION (CPSES)~ UNIT 2 00CKET NO. 50-446 CORRODED HILTI BOLTS SDAR CP-91 003 (INTERIM REPORT)
Gen tl emer;-
On June 11, 1W 1 TU Electric orally notified the NRC of a deficiency involving the corrosion of installed Hilti Kwik Bolts (HKB). This condition was identified when an HKB on a floor mounted pipe support broke during retorquing.
Examination of the broken bolt identified a significant reauction in cross sectional area due to corrosion. This is an interim report of a potentially reportable item under the provisions of 10CFR50.55(e). Our last interim report on this issue was logged TXX-91246 dated July 10, 1991.
We are continuing our evulua'*3n of this issue in accordance with our Procedure 2IH-5.24 " Selection, Inspection and Evcluation of Hilti Anchors in Potentially Flooded Areas in Unit 2".
The next report on this issue will be provided by December 16, 1991.
Sincerely, i
William J. Cahill, Jr.
C By:
D. R. Woodlan Docket Licensing Manager CLW/clw c - Mr. R. D. Hartin, Region IV Hr. T. A. Bergman, NRR Resident Inspectors, CPSES (2) 0 b6 ) l n
1 c:.r r " q h
9109200361 910?17 L
PDR ADOCK 05000446 400 N rth clive street t B. si Dallas. Texas 75201
/
.