Director,L0ffice of Resource Management.

' Monthly Operating' Report Page 2 November'14, 1983

. ATTACHMENT I

- AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50/395 UNIT V.

C.

SUMMER I DATE 11/14/83 COMPLETED BY G.

A.

Loignon TELEPHONE (803) 345-5209

' MONTH OCTOBER 1983 DAY' AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) 1.

894 17 816

~.

894 18.

-853 2

3..

893 19 893 4.

894 20.

319

'5.

892 21.

100 22.

224 6.

892' 7

893 23 43 8.

885 24.

654

=9 893 25.

892

10..

892 26.

893

11. _

893 27 894 12.1

-893 28.

895

'13

'860 29 894

-14.:

824 30.

894

.15. -

821 31.

893 16.

819

[DkkDO O

DR R

______x

..i LDirector,40ffice of Resource Management

' Monthly-Operating: Report

Page 3' November 14,'1983 ATTACHMENT II

-OPERATING' DATA REPORT DOCKET NO.

50/395 UNIT V.

C. SUMMER I DATE 11/14/63 COMPLETED BY G.

A.

Loignon TELEPHONE (603) 345-5209 OPERATING STATUS 1.-Reporting Period:

OCTOBER 1983 Gross Hours in Reporting Period:

745 L2.JCurrently Authorized Power Level (MWt):

2775 Max.; Depend. Capacity (MWe-Net):

N/A Design: Electrical Rating (MWe-Net):

900 13.-Power-Level to.which restricted (If Any)(MWe-Net):

N/A L4. Reasons for Restrictions (If Any):

THIS MONTH YR TO DATE CUMULATIVE 5.cNumber:of' Hours-Reactor'Was Critical 711.4 5532.1 6838.9

16. Reactor Reserve Shutdown Hours 0

0

-0

_7.

Hours. Generator'on Line 689 4 5375.8 6137 1

8. Unit:ReservelShutdown Hours 0

0 0

9 10ross' Thermal _EnergyL0enerated (MWH)

-1,610,240 11,506,707 12,302,580 10.fGross: Electrical. Energy Generated (MWH).

581,251 3,566,471 3,779,667 607,880 3,781,572 3,997,789

11. Net Electrical: Energy Generated (MWH)

C12.-Reactor. Service Factor N/A N/A N/A

'13.1 Reactor Availability Factor N/A N/A N/A

14. Unit ~ Service Factor N/A N/A N/A
15. Unit' Availability Factor N/A N/A N/A L16. Unit Capacity Factor (Using MDC)

N/A N/A N/A

! 117 9 Unit'. Capacity Factor 1(Using. Design MWe)

N/A N/A N/A 18.; Unit Forced Outage Rate-N/A N/A N/A J19. Shutdowns' Scheduled Over Next.6 Months (Type, Date, and Duration of Each):

~

-Steam Generator Eddy Current, November 23, 1983 (approximately 15 days).

J20.:IfLShut Down at End of Report Period,' Estimated Date of Startup:

N/A

~21 1 Units in-Test Status (Prior to Commerical Operation):

~

FORECAST ACHIEVED Initial Criticality 10-20-82 10-22-82 Initia1' Electricity 11-17-82 11-16-82 Commercial Operation 01-01-84

,e-

.s

-u

.m r-e 4

y-

n

[

y l r (Dirsetor,3'ffi,ce_of~ Resource Management 0

M:nthly: Operating Report

- Pcge _ 4.-

Nov;mber :14, 1983/

' ATTACHMENT III-

-UNIT SHUTDOWNS AND POWER REDUCTIONS-DOCKET NO.'

50/395 UNIT V.

C.

SUMMER I DATE 11/14/63

. COMPLETED BY-G.

A.

Loignon<

TELEPHONE (803) 345-5209 (1)

METHOD OF (2)

TYPE-SHUTTING DOWN

.F: FORCED DURATION THE. REACTOR OR

-CORRECTIVE ACTIONS /

NO.

-DATE S: SCHEDULED (HOURS)

REASON REDUCING POWER COMMENTS

';ML 831020 F

26.1-A 2

20) Faulty wire shorted

tripping Circ. Water Pumps.

21' 831022 F-2 9.' 6 '

A 2-

21) Leak in Turbine EHC-System.

ev

-v-

,)_i

' Director,-Office of Resource Management

Monthly Operating Report:

-Page 5 November'14, 1983 ATTACHMENT IV

' NARRATIVE

SUMMARY

10F OPERATING EXPERIENCE-

! Virgil C.l Summer: Nuclear Station, Unit.No. 1, continued power Joperationiduring the month.of October 1983 L0n' October 20, 1983, at'0905 hours0.0105 days <br />0.251 hours <br />0.0015 weeks <br />3.443525e-4 months <br />, the Plant was manually tripped-from approximately-90% power following the loss.of.all

-Circulating Water Pumps._ The pumps had tripped. automatically.

when'one of the flood protection level switches-was accidently.

shorted'by plant _ personnel.

The-2/3. logic for flood protection wasLcompleted bytthis short since-the' supply breaker.for the s

redundant switches.was incorrectly.:in the "0FF" position.

The cause is attributed to' personnel error. ~ Plant performance during

the eventJwas asfexpected.with no' events of~ safety significance.

On= October.22,-1983,:atL1053 hours,-the plant'was manually L

tripped from approximately 77% power..The trip was initiated whenithe; Shift Supervisor determined that an oil leak in the EHC System piping was high enough to preclude. running the plant back in a controlled. manner.

Plant response to the transient was normal

_and the source offthe= leak subsequently repaired.

~

90n October.31,-1983, operation was continuing at approximately 100%

power.

~

k

j',

l ur.

SOUTH CAROLINA ELECTRIC & GAS COMPANY post oppics 7e4 -

COLUMelA. SOUTH CAROLINA 29218 '

~O. W. DixON. JR.

Vice PossiosNT NucLEAm OrspAT:Jms November 14, 1983 LDirector,-Office.of Resource Management U. S. Nuclear _ Regulatory Commission

.MNBB 7602 Washington, DC 20555 ATTN:

Mr. Learned it. Barry

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Monthly Operating Report

Dear.Mr. Barry:

Please find enclosed the-October 1983 Monthly Operating' Report for.

.the Virgil C. Summer' Nuclear Station Unit No. 1 as required by Technical Specification 6.9.1.10.

If-there are-any questions, please call us at your convenience.-

Ver trul yours,_

N O. W.

ixo,

r.

N GAL:0WD:mac Attachment cc:

V.10. Summer C. A.

Price E.-C.

Roberts-A. R. Koon E. H. Crews' O. L. Ligon (NSRC)

T. C. Nichols, Jr./0. W. Dixon, Jr.

G. J. Braddick H. N.!Cyrus D. J.

Richards H. R. Denton-NRC Res. Inspector J. P. O'Reilly-J. B.

Knotts, Jr.

" Group. Managers INPO Records Center O. S. Bradham NPCF-R. B._Clary File (Lic./Eng.)

l

\\

-