ML20082P938
| ML20082P938 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 09/06/1991 |
| From: | Woodard J ALABAMA POWER CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| 91-005, 91-5, NUDOCS 9109110163 | |
| Download: ML20082P938 (2) | |
Text
Awtwna row cmina, 40 inve res Center Pc.o e, y g
Post Dace CO,t095 B<rmcfam icana 3r,20t Te;ephone 205 MS 50&,
J L
th M IPO M f $7,$.d Septa bar 6, 1991 n y.,
ra~m om
. w +,;,,,,, w,.,,,
Docket Nos. 50-348 50-364 1
I U. S. Nuclear Regulatory C. mission ATTN:
Document Control Desk Washington, DC 20555 Joseph M. Farley Nuclear Plant Special Report 91-005 Fire Dampers Inoperable Due To Failure To Close With Maximum Air Flow Gentlemen:
In accordance with the requirements of Technical Specification 3.7.12, the enclosed Special Repo.
No.91-005 is submitted.
Respectfully submitted, d)
JDW/BHW: map 0914 Enclosure cc: Mr. S. D. Ebneter Mr. S. T. Hoffman Mr. G. F. M'"well i
9109110163 910906 DR ADOCK 05000348
'f If,e
/
g PDR h
T
~
Joseph H. Farley Nuclear Plant Special Report No.91-005 -
Fire Dampers Inoperable Due To Failure To Close With Maximum Air Flow During the performance of fire damper testing, the four fire dampers listed below did not meet the acceptance criterion of closing with maximum air flow and were declared inoperable.
Each damper was declared inoperable on
- the date it was tested.
Design change requests have been submitted to modify these dampers to ensure proper operation under all system conditions.
Damper Numbqr Date Tested Desian Chance Reauest Number 121-115-34 08-08-91 91-1-7640 1-121-115-35 08-08-91 91-1-7641 2-121-133-01 08-15-91 91-2-7647 1-139-119-07 08-16-91 91-1-7649 The modifications to these dampers are expected to be completed by 09-20-91.
Technical Specification 3.7.12 requires these dampers be returned to operable status within seven days or a Special Report must be submitted within the following 30 days.
Therefore, this Special Report is being submitted. All Technical Specification action statement requirements for
-these fire dampers are being met.
1 a
I
-.