Text
-
PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 PHILADELPHI A. PA.19101 g
,.}
JOHN S. KEMPER VIC E-PR ES4 D E NT smessera nsees ano masamacH L
Mr. Thomas E. Murley, Director United States Nuclear Regulatory Commission Of fice of Inspection and Enforcement, Region I 631 Park Avenue King of Prussia, PA 19406
Subject:
USNRC IE Region Letter dated October 5,1983 l
RE: Site Inspection of August 1 - September 2,1983 Inspection Report No. 50-352/83-11 1
Limerick Genera ting S tation Unit 1 File:
QUAL 1-2-2 (3 52/83-11)
Dear Mr. Murley:
In response to the subject letter.regarding items identified during the subject inspection of construction activities aitthorized by NRC License Nos. CPPR-106, we transmit herewith the following:
Attachment I - Response to Appendix A l
Also enclosed is an af fidavit relating to the response.
l l
Should you have any question concerning these items, we would be pleased to discuss them with you.
Sincerely,
$.,A_
JPE/drd/C/3 l
Attachment Copy to:
Director of Inspection and Enforement United States Nuclear Regulatory Commission Washington, DC 20555 l
S. K. Chaudhary, USNRC Resident Inspector 8311280276 831121 F'DR ADOCK 05000 0
,a ATTACHMENT I RESPONSE TO APPENDIX A VIOLATION A 10CFR50, Appendix B, Criterion IX requires that measures shall be established to assure that welding is accomplished by qualified personnel. The G.E.
General Welding Procedure LMI-GMP-1, Revision 0 specifies the requirements of ASME,Section IX for welder qualification as a project requirement.
ASME, B&PV Code,Section IX, Paragraph QW-303.2 states in part: " Welders who make fillet welds on pipe or tube less than 2 7/8" 0.D. must pass the pipe fillet weld test per QW-452.4.
Contrary to the above, on August 24, 1983, the inspector determined th'at two welders perf orming welds on in-core housing to guide tube socket fillet welds were not qualified to perform such pipe welds because they were qualified by plate fillet test assembly.
The guide tubes are less than 2 7/8" 0.D.
RESPONSE TO VIOLATION A To determine the extent of the problem, a review of welders' performance records and the weld issue log was conducted.
The performance records of two welders were found to be in tror and have been corrected.
No additional instances of welders perrorming outside the limits of their qualifications were identified.
The welds made by tbc identified unqualified welders were removed and replaced by qualified welders.
i l
To prevent a recurrence, the involved GE A&ESO subcontract personnel were instructed in the requirements of Section IX.
I 1/2 50-352/83-11 l
r C0fMONWEALTH OF PENNSYLVANIA ss.
COUNTY OF PHILADELPHIA JOHN S. KEMPER, being first duly sworn, deposes and says:
That he is Vice President of Philadelphia Electric Company, the holder of Construction Permit CPPR-106 for Limerick Generating Station Unit 1; that he has read the foregoing Response to Inspection Report No. 50-352/83-11 and knows the contents thereof; and that the statements and matters set forth therein are true and correct to the best of his knowledge, information and belief.
M f / ~~. l. -
Subscribed and sworn to before me this M day Of 6./dw PATRICIA D. SCHoLL Netary Public, Phibdelphia, Philedc4hia Co.
My Commission Expires february 10.1986