ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 UTTLE ROCK, ARKANSAS 72203 (501) 371-4000 November 14, 1983 OLC-113-13 U.S. Nuclear Regulatory Commission Copy No. Copy No. I-110 7920 Norfolk Avenue Bethesda, MD 20545

Subject:

FSAR Q-List Tabs Attached are two Q-list tabs for insertion in your AN'O Final Safety Analysis Report (FSAR).

Insert these tabs in your ANO-1 FSAR, Chapter 1, before page 1.10-8 and in your ANO-2 FSAR, Chapter 3, before page 3.13-21.

Also, replace pages 1.10-7 and 1.10-8 in your ANO-1 FSAR with the attached pages.

Indicate receipt of these tabs and replacement pages by signing below and returning this letter to Sally Benson, Licensing Section, P. O. Box 551, Little Rock, AR 72201.

Very truly yours, hn R. Marshall Manager, Licensing JRM:SAB:s1 Attachments Signed:

Date:

Copy No.

kDdk$0pK05000313 93 831324 K

l PDR

>)

r lP MEMBEA MIDDLE SOUTH UTIUTIES SYSTEM

(

~

(

ARKANSAS NUCLEAR ONE Unit 1

,-z Table 1-1 (continued)

U Reactor Building Coolers Type Recirculation Fan-Coil Unit Number of Units 4

Capacity, Each, at Accident, Btu /hr 60 x 106 Core Flooding System Numbar of Tanks 2

Total Water Volume, Each, f t3 1,410 Reactor Building Spray Number of Pumps 2

Capacity, Each, gpm 1500 Spray additive for lodine Removal

  • Sodium Hydroxide Emergency Power Type Diesel Engine Generators Quantity / Capacity 2/2750 kw, 4160 volts Exclusion Radius, mi 0.65

[v-R

\\

Low Population Radius, mi 4.0 Reactor Building Type Prestressed concrete Leak Rate, %

.2 Volume, ft3 2,087,000 Design Pressure, psig 59 Emergency Feedwater Pump Type Horizontal centr.

(One steam turbine drive one motor drive)

Head, psi 1100 Flow, gpm 760

  • 1+

Sodium thiosulfate and sodium hydroxide were used for iodine removal in the original design.

However, only sodium hydroxide is now used for f( ')

this function.

+1+

el* - Amendment No. 1 1.10-7

(

~

-s

ARKANSAS NUCLEAR ONE Unit 1 Table 1-2 ARKANSAS NUCLEAR ONE-UNIT 1 NUCLEAR QUALITY ASSURANCE Q LIST The basic purpose of this list is to specifically identify those items within the scope of the Nuclear Quality Assurance Program.

Items listed require special consideration during

design, manufacture, and construction.

d The list is to include all Class 1 structures, systems, and equipment.

Class 1 structures systems and equipment are those whose failure could cause uncontrolled release of radioactivity or those essential for the safe shutdoiin and the immediate and long-term operation following a Loss of Coolant Accident (LOCA).

When structures, systems or equipment as a whole are on this list, portions not associated with a loss of safety function are not meant to be included.

This includes:

Engineered Safeguards as destied in Chaotut 6.

The Q List is divided into five major sections:

1.

CIVIL STRUCT!EAL 2.

NUCLEAR MECHAhlCAL 3.

CONVENTIONAL MECHANICAL 4.

AUXILIARY ELECTRICAL 5.

ARCHITECTURAL O

1.10-8

.