Text
-
i A
N) Commonwealth Edison Qu d Citi;s Nucber P:wer Station
,m C
22710 206 Avenue N:rth 7
Cordova, Illinois 61242 Telephone 309/654 2241 l
NJK-83-395 November 1, 1983 Mr. Edson G, Case, Deputy Director Of fice of Nuclear Reactor Regulation U, S. Nuclear Regula tory Commission Washington, D, C, 20555
Dear Mr. Case:
Encioned please find a listing of those chances, tests, and experi-ments completed during the month of October, : 983, for Quad-Cities Station Units 1 and 2, DPR-29 and DPR-30.
A summary of the safety evaluation is being reported in compliance with 10 CFR 50.59.
Thirty-nine copies are provided for your use.
Very truly yours, COMMONWEALTH EDISON COMPANY QUAD-CITIES NUCLEAR POWER STATION
//
r N
J, Ka11vlanakis Station Superintendent bb Enclosu re cc:
B. Rybak i\\
8311170395 831101 PDR ADOCK 05000254 R
H-4-1/2-79-12 Shared Diesel Generator Local Control Description This modification provides control of the 1/2 Diesel Generator from the 1/2 Diesel Generator room. There is a transfer switch which enables the separation of the Diesel Generator electrical controls in the Control Room from those in the Diesel Generator room when the switch is in the
" local control" position. This will ensure faults in the Control Room cables or connecting control cabling-will not influence the Diesel Generator operation.
This installation is-part of-Supplement I of the Fire Protection Safe Shutdown Analysis.
Evaluation The local control' feature for the 1/2 Diesel Generator will increase the availability of the equipnent by being able to operate the equipnent in the e tent of a fire.in the Control Room, Cable Tunnel, or Auxiliary Electric' Equipnent room.. The emergency' auto-start feature of the Diesel Generator remains unchanged. The ability to provide emergency AC' power is thus increased.
_ _ _.. _....._