ML20081C921

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Unverified Computer Code in Design of Main Feedwater Pipe Supports.Review & Evaluation Complete.Event Not Reportable Per 10CFR50.55(e) & Part 21. Unverified Valve Computer Subroutine Replaced by Bechtel
ML20081C921
Person / Time
Site: Vogtle  
Issue date: 03/07/1984
From: Foster D
GEORGIA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
GN-325, NUDOCS 8403150069
Download: ML20081C921 (1)


Text

Georgia Power Company Route 2. Box 299A Waynesboro Georgia 30830 Telephone 404 554-9961 404 724-8114 A

B4 MAfil2 P l : 07 March 7, 1984 United States Nuclear Regulatory Commission File: X78G03-M34 Office of Inspection and Enforcement Log:

GN-325 Region II-Suite 3100 101 Marietta Street Atlanta, Georgia 30303 Refarence: Vogtle Electric Generating Plant-Units 1 and 2, 50-424, 50-425; Unverified Computer Code-Main Feedwater Pipe Supports; also GN-310, dated 2/7/84.

Attention: Mr. James P. O'Reilly Gentlemen:

In our previous correspondence to the NRC, Georgia Power Company indi-cated that the NRC would be notified by March 9,1984, of the results of our evaluation of the use of an unverified computer code in the design of main feedwater pipe supports. Georgia Power Company has completed its review and evaluation of this event and has concluded that it is not reportable pursuant to the requirements of 10 CFR 50.55 (e) and 10 CFR 21.

Bechtel Power Corporation replaced the unverified RELAP-5/ MOD 1 inertial valve computer subroutine with a verified RELAP-5/ MOD 1 servo valve computer subroutine and performed a new calculation using additional design data from the valve manufacturer. The results of this evaluation substantiates the adequacy of the existing design to assure safe operation.

Since the NRC has defined a "significant deficiency" as one having an adverse effect upon, or. likely to adversely affect, the safe operation of the plant, Georgia Power Company has concluded that this event does not constitute a significant deficiency in design or construction.

This response contains no proprietory information and may be placed in the NRC Public Document Room upon receipt.

/

Yours-truly, '

I 8403150069 840307 gDRADOCK05000g2 D. 0.. Foster REF/D0F/tdm i

xc:

U. S. Nuclear Regulatory Commission i

Document Control Desk C'FFICIAL COM Washington, D. C.

20555 T[Z7 g

l xc:

R. J. Kelly D. E. Dutton J. A. Bailey L. T. Gucwa R. E. Conway W. F.. Sanders

0. Batum M. Malcom G. F. Head R. H. Pinson G. Bockhold H. H. Gregory-C. W. Hayes P. D. Rice ~

B. M. Guthrie J. T. Beckham D. M. MacLemore R. A. Thomas E. D. Groover J. L. Vota-

\\