Amends 203 & 181 to Licenses DPR-53 & DPR-69,respectively, Re Changes to TS to Include Verification That EDG High Crankcase Pressure Trip Bypassed When Safety Signal Present
ML20081A055
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 03/03/1995
From: Marsh L
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20081A058 List:
References
NUDOCS 9503140457
Download: ML20081A055 (8)


Text

_.

. ~

-9 a

s f*

bl I

s 4

l[

  • t UNITED STATES -

q *-

[

NUCLEAR REGULATORY COMMISSION

.I o

, ASHINGTON, D.C. 20066-0001 W

4, BALTINDRE GAS AND ELECTRIC COMPANY DOCKET ND. 50-317 j!

CALVERT CLIFFS NUCLEAR POWER PLANT UNIT NO. I

-j 4

AMEleMENT TO FACILITY OPERATING LICENSE q

Amendment No. 203 i

License No. DPR-53 1

1 1.

The Nuclear Regulatory Commission (the Commission) has found that:

q A.

The application for amendment by Baltimore Gas and Electric Company (the licensee) dated August 2, 1994, complies with the standards and j

requirements of the Atomic Energy Act of 1954, as' amended (the Act) i and the Commission's rules and regulations set forth in 10 CFR-Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (1) that the-activities authorized by this amendment can be conducted without endangering' the' health and -

safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations;;

D.

The issuance of this amendment will not be inimical'to the' common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51' of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical

)

Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.2. of Facility Operating License No. DPR-53 is hereby amended to read as follows:

i i

9503140457 950303 PDR ADOCK 05000317 P

PDR

i

2. -

Technical Snecifications The Technical Specifications contained in Appendices A and B, as revised through knendment No. 203, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance and shall be implemented within 30. days.

i FOR THE NUCLEAR REGULATORY C0fMISSION Ledyard B. Narsh, Director Project Directorate I-1 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications l

Date of Issuance:

March 3, 1995 i

l 1

'. p""o%

y-ht UNITED STATES g

.g NUCLEAR REGULATORY COMMISSION t

WASHINGTON, D.C. 20066-0001

\\..... j/

i BALTIMDRE GAS AND ELECTRIC COMPANY

)

DDCKET NO. 50-318 CALVERT CLIFFS NUCLEAR POWER PLANT. UNIT NO. 2 l

.j AME9EMENT TO FACILITY OPERATING LICENSE Amendment No. 181 License No. DPR-69 j

1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Baltimore Gas ar;d Electric Company-(the licensee) dated August 2, 1994, complies with the' standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application,

[

the provisions of the Act, and the rules and regulations of the Commission C..There is reasonable assurance (1) that the activities authorized f

by this amendment can be conducted without endangering the health and' safety of the public, and (ii) that such activities will be conducted l

in compliance with the Commission's regulations;-

j I

D.

The issuance of this amendment will not be inimical to the common i

defense and security or to the health and safety of the public;- and E.

The issuance of this amendment is in accordance with 10'CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

i 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.2. of Faaility Operating License No. DPR-69 is hereby amended to read as follows.

1

~...,

~.-

'{.

2--

t

}

2.

Technical Snecificationh i

J l

The Technical Specifications contained in Appendices.A and 8,.as revised through Amendment No.181,iare hereby incorporated in the license. The

-licensee shall operate the! facility in accordance with the Technical l

Specifications.

3.

This license ahnendment is eff.ective as of the date of its issuance and shall be' implemented within 30 days.

FOR THE NUCLEAR REGULATORY COMi!SSION Ledyard B. Marsh, Director Project Directorate I-1 Division of Reactor Projects - I/II..

i Office of Nuclear Reactor Regulation Attachment.

Changes to the Technical Specifications Date of Issuance: Macch 3, 1995 l

i k

1 I

i l

~

Mr. Robert E. Denton Calvert Cliffs Nuclear Power Plant l

Baltimore Gas & Electric Company Unit Nos. I and 2 cc:

Mr. Hagner Mister, President Mr. Joseph H. Walter Calvert County Board of Engineering Division Comissioners Public Service Comission of i

175 Main Street Maryland j

Prince Frederick, MD 1!0678 6 St. Paul Centre i

Baltimore, MD 21202-6806 D. A. Brune, Esquire General Counsel Kristen A. Burger, Esquire Baltimore Gas and Elect ric Company Maryland People's Counsel P. O. Box 1475 6 St. Paul Centre Baltimore, MD 21203 Suite 2102 i

Baltimore, MD 21202-1631 Jay E. Silberg, Esquire Shaw, Pittman, Potts and Trowbridge Patricia T. Birnie, Esquire 2300 N Street, NW Co-Director Washington, DC 20037 Maryland Safe Energy Coalition P. O. Box 33111 Mr. G. L. Detter, Director, NRM Baltimore, MD 21218 Calvert Cliffs Nuclear Power Plant 4

1650 Calvert Cliffs Parkway Mr. Larry Bell Lusby, MD 20657-4702 NRC Technical Training Center 5700 Brainerd Road Resident Inspector Chattanooga, TN 37411-4017 c/o U.S. Nuclear Regulatory Comission P. O. Box 287 St. Leonard, MD 20685 Mr. Richard I. McLean Administrator - Radioecology Department of Natural Resources 580 Taylor Avenue Tawes State Office Building B3 Annapolis, MD 21401 Regional Administrator, Region I i

U.S. Nuclear Regulatory Comission 475 Allendale Road King of Prussia, PA 19406

1 s ATTACMENT TO LICENSE AMENDMENTS AMENDMENT N0. 203 FACILITY OPERATING LICENSE NO. DPR-53

~

AMENDMENT N0. 181 FACILITY OPERATING LICENSE NO. DPR-69

-DOCKET NOS. 50-317 AND 50-318 Revise Appendix A as follows:

Remove Pace Insert Pace 3/4 8-5 3/4 8-5 i

w

^

3/4.8. ELECTRICAL POWER SYSTEMS ~

l

. SURVEILLANCE REQUIREMENTS (Continued)

I

/

c.

At least once per 184 days by verifying the diesel starts lfrom.

510 seconds.} ion and accelerates to at. least 900 rpm in ambient condi d.

At least once per REFUELING INTERVAL by:

1 1.

Subjecting the. diesel to an inspection in accordance with procedures prepared in conjunction with its, manufacturer's recommendations for this class of standby service.

2.

Verifying the generator capability to reject a load of 1 500 hp without tripping.

1 3.

Simulating a loss of offsite power in conjunction with a safety injection actuation-test signal, and:

~

l a) Verifying de-energization of the emergency busses and j

load shedding from the emergency busses.

b) Verifying the diesel starts from ambient condition' on the auto-start signal, energizes the emergency busses with permanently connected loads, energizes the auto-connected i

emergency loads through the load sequencer and operates for > 5 minutes while its generator is loaded with the emergency loads.*

]

c) Verifying that the high jacket coolant temperature, high crankcase pressure, and low jacket coolant pressure trips 1

are automatically Actuation Signal.,, bypassed on a Safety Injection 4.

Verifying the diesel generator operates for 160 minutes while loaded to 1 2500 kW.

5.

Verifying that the auto-connected loads to.each _ diesel generator do not exceed the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of each diesel generator.

All engine starts for the purpose of this Surveillance Requirement may be preceded by an engine pre-lube period recommended by the manufacturer so that mechanical wear and stress on the diesel engine is minimized.

The high crankcase pressure trip bypass verification is applicable after the trip bypass is installed on the diesel engine being tested.

Modifications are to be co;npleted by February 28, 1996.

CALVERT CLIFFS - UNIT 1 3/4 8-5 Amendment No. 203

=

'3/4.8 ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)-

L c.

At least once per 184 days by verifying the diesel starts from

<10 seconds.}ionandacceleratestoatleast900'rpmin ambient condi d.

At least once per REFUELING INTERVAL by:

1.

Subjecting the diesel to an inspection in accordance with' procedures prepared in conjunction with its manufacturer's recommendations for this class of standby service.

I 2.

Verifying the generator capability to reject a load of I 500 hp without tripping.

3.

Simulating a loss of offsite power in conjunction with a safety injection actuation test signal, and:

a) Verifying de-energization of the emergency busses and load shedding from the emergency busses, b) Verifying the diesel starts from ambient condition on the auto-start signal, energizes the emergency busses with pennanently connected loads, energizes the auto-connected emergency loads through the load sequencer and operates for 15 minutes while its generator is loaded with the emergency. loads.*

l c) Verifying that the high jacket coolant temperature, high crankcase pressure, and low Jacket coolant pressure trips Actuation Signal,, bypassed on a Safety Injection are automatically t

4.

Verifying the diesel generator operates for 160 minutes-while loaded to t 2500 kW.

5.

Verifying that the auto-connected loads to each diesel generator do not exceed the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of each diesel generator.

i All engine starts for the purpose of this Surveillance Requirement may be preceded by an engine pre-lube period recommended by the manufacturer so that mechanical wear and stress on the diesel engine is minimized.

The high crankcase pressure trip bypass verification is applicable after the trip bypass is installed on the diesel engine being tested.

Modifications are to be completed by February 28, 1996.

CALVERT CLIFFS - UNIT 2 3/4 8-5 Amendment No. 181

,