'T March'3, 19951

h

% [/h.

{

TN

~-

<SP o i

UNITED STATES OF AMERICA D

't i

. NUCLEAR REGULATORY COMMISSION Before the Atomic Safety and'Licensina Board

~

)

In the Matter of

)

Docket Nos. 50-424-OLA-3 r

E

)

50-425-OLA-3 l

-GEORGIA POWER COMPANY,

)

et al.

)

.Re: License Amendment

)

)

(Transfer to Southern

-(Vogtle Electric Generating

)

Nuclear) f Plant, Units 1 and-2)

)

)

ASLBP No. 93 -671-01-OLA-3 i

GEORGIA POWER COMPANY'S STATEMENT OF' MATERIAL ~ FACTS AS TO s

WHICH THERE IS NO GENUINE ISSUE TO BE HEARD:REGARDING f

INTERVENOR'S AIR OUALITY STATEMENTS ALLEGATION 1

Pursuant-to 10 C.F.R. $ 2.749(a), Georgia Power Company 1

-(" Georgia Power") hereby submits its statement of material facts' i

as to which there is no genuine issue to'be heard:

l i

?

1.

-In March 1990, Plant Vogtle personnel and an NRC inspector, inspected the diesel generator control air filters and-concluded j

that the filters looked new (e.g., there were no_ rust particles or other evidence of moisture in the control air system).

(

2.

On April 6, 1990, Mr. Mosbaugh praised Engineering personnel

-for the work they did on the diesels and how well they interfaced with the Incident Investigation Team ("IIT") and that the IIT

~

9503130100 9 PDR ADOCK 0 0

P

, _ - _ _.. _.... ~ __--...

f2 o

g, w

Y

~would be satisfied on the' diesel issues:sufficiently to' release

~

the hold.on startup.ofjvogtle Unit.-l.

J

s 3.

By; April'6, 1990, the IIT was informedc of' higher.than; expected dew-point measurements and that preliminary indications were that the high' readings were due to a cad dew point sensor instrument.

i:

4.

On April 6, 1990,. Georgia Power performed an inspection of-the 1A diesel air receiver which was witnessed by an NRC i

inspector.

Neither the. rust nor the oil residue found duringLthe inspection was unusual or of concern to Georgia Power or NRC personnel.

5.

On April 9, 1990, NRC representatives were informed of a.

recent high dew point reading of 60.9'F on the 2A diesel air receiver and that it was attributable to the associated' air dryer being-turned off a few days earlier.

6.

On April 9-10, 1990, the NRC was informed orally and-in writing of historic unacceptable dew' points.

2

,p;

7-s

-)

a 1

7.

j g

During an internal meeting of; Plant Vogtle engineering' i

personnel on the morningfof April 11, 1990 there was~a consensus:

i a

that the
dew point acceptance criteria of 50 *F had not always l

i been met in the past, but that based on their engineering

~

' judgment'the air quality was acceptable.

q

-f.

8.

In April, 1990, the diesel manufacturer (Cooper) advised Georgia Power personnel that they considered the air quality of I

the Vogtle diesel control air to be acceptable.

]

9.

t During a discussion with the IIT on April-11, 1990, Plant

+

Vogtle personnel informed-the NRC that they believed the current 3

air quality of-the diesels to be satisfactory although, during 1988, one of the air dryers was out of service for maintenance.-

i 10.

i The diesel air quality statements in Georgia Power's April 9,

1990 letter to NRC discussed only the current status of the t

i diesels' instrument air quality and conveyed GPC'sfjudgment that the diesel control air quality relative to moisture or " humidity" -

was satisfactory at that time.

?

l 3

i i

r 11.

As of April 9, 1990, the NRC was satisfied that the diesel _

f control air quality was acceptable and that the Vogtle' diesel

. generators were operable and reliable.

i s

t i

12.

The August 1990 NRC Operational Safety Inspection concluded that Georgia Power did have an adequate basis to assess the quality of the diesel' starting air syst-on April 9, 1990 and they did not find that Georgia Power misrepresented the diesel air quality in the April 9 letter.

r 13.

During a 1994 inspection, the NRC Staff concluded that Plant j

i Vogtle' maintenance documentation provided no indication that-water had been detected in the control and protection portion of the system at any time.

The inspectors further concluded that f

water formation in the air system was unlikely because of the i

decrease in dew point associated with the pressure reduction in the control air system.

t 14.

on February 13, 1995, the NRC concluded that the air quality statements in Georgia Power's April 9 letter were sufficient in f

4 6

4 i

l f

r i

i 3

. ;f L 4

g scope and GPC had an adequate technical basis to support a finding'that air quality was acceptable.

r-7 L

I i

g Respec ully. submitted, F

r

.l

/A James E. To3er John Lamberski f

TROUTMAN SANDERS Suite 5200 l

600 Peachtree Street, N.E.

i Atlanta, GA 30308-2216 (404) 885-3360

'i Ernest L. Blake David R. Lewis SHAW, PITTMAN, POTTS & TROWBRIDGE 2300 N Street, N.W.

Washington, D.C.

20337 (202) 663-8084 Counsel for Georgia Power Company i

Dated:

March 3, 1995 t

i l

5 5

i

{

i

+

i 5

t u

3 ;y_,.

p -

Y t

March 3, 1995 l

UNITED STATES OF AMERICA

{

NUCLEAR REGULATORY COMMISSION Before the Atomic Safety and Licensina Board

).

In:the Matter of

)

Docket Nos. 50-424-OLA-3

.)

50-425-OLA-3 GEORGIA POWER COMPANY,-

)

et al.

)

Re: License Amendment i

)

(Transfer to Southern

.. i (Vogtle Electric Generating

)

Nuclear)

Plant, Units 1 and 2)

)

)

ASLBP No. 93-671-01-OLA-3 APPENDIX TO GEORGIA POWER COMPANY'S MOTION FOR

SUMMARY

DISPOSITION i

s OP ' INTERVENOR'S AIR OUALITY STATEMENTS AT TM-4 TION b

Affidavit of C. Kenneth McCoy, dated March 3, 1995-i

+

("McCoy Aff.");

Affidavit of Milton D. Hunt, dated March 1, 1995-("Hynt

+

Aff.");

Deposition of Kenneth S. Burr taken on May 24, 1994 l

l

(" Burr Dep.");

Deposition of Kenneth Holmes taken on July 7, 1994

'l

(" Holmes Dep.");

Deposition of Paul Kochery taken on July 6, 1994 ("Koc-hery Dep.");

l Deposition of Kenneth Stokes taken on July 5, 1994

(" Stokes Dep.");

L 3

)

l l

\\

1

.)