Responds to NRC Re Violations Noted in IE Insp Rept 50-482/83-25.Corrective Actions:Nonconformance Rept Generated to Document Identified Welding Concern & to Provide Appropriate Controls
ML20080P144
Person / Time
Site: Wolf Creek 
Issue date: 12/22/1983
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Gagliardo J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20080P125 List:
References
KMLNRC-83-166, NUDOCS 8402220452
Download: ML20080P144 (3)


Text

-

1 KANSAS GAS AND ELECTRIC COMPANY THE ELECTF4tC COMPANY

@LENN L.

et O E S T E R WCf PRES 10ENT + NUCLEAM December 22, 1983

%W- @ MDW1W-

  • Mr. J.E. Gagliardo, Acting Chief Reactor Projects Branch 2

,s U.S. Nuclear Regulatory Commission iL g2gg Region IV l g 611 Ryan Plaza Drive, Suite 1000 ylj d

Arlington, Texas 76011 KMLNRC 83-166 Re: Docket No. STN 50-482 Subj: Response to Inspection Report STN 50-482/83-25

Dear Mr. Gagliardo:

This letter is written in response to your letter of November 22, 1983, which transmitted Inspection Report STN 50-482/83-25. As requested, the violation identified in the Inspection Report is being addressed in three parts:

a) The corrective steps which have been taken and the results achieved; b) Corrective steps which will be taken to avoid further violations; and c) The date when full compliance will be achieved.

VI_O_LATION : Failure to Follow and/or Implement Quality Requirements Finding:

10 CFR Part 50, Appendix B, Criterion V, requires, in part, that activities affecting quality shall be prescribed by instructions, procedures, or drawings and shall be accomplished in accordance with these instructions, procedures, or drawings.

Bechtel Specification No. 10466-M-618.2, " Technical Specification for Field Installation of Ductwork (Q listed) for the Standardized Nuclear Unit Power Plant System (SNUPPS)," paragraph 5.8 states :

8402220452 840113 PDR ADOCK 05000482 G

PDR 201 N. Merket - WicNta, Kansas - Mail Address: PO. Box 208 I Wichita, Kansas 67201 -, Telephone: Area Code (316) 261-6451

1 z; * '

Mr.LJ.E. Gagliardo KMLNRC 83-166 December 22, 1983 Finding ' -(continued) :

" Welding of structural members shall be. in accordance with

American Welding Society (AWS) ' D.l.l."

AWS D l.1-75, paragraph 5.5.2, requires that when essential-

.. changes are made in a welding procedure, a new procedure must be established by ~ qualification.

Paragraph.5.5.2.1, for Shielded Metal Arc Welding (SMAW),. further defines the omission of. backing material as an eccential change.

Daniel International Corporation (DIC) Technique Sheet N-1-1-A-18 is qualified for AWS plug welds for the SMAW process using the mating surface of the lapped material as a backing material.

. Con *,rary to the 'above, DIC Technique Sheet N-1-1-A-18 was used for raetoration of mislocated holes in Pieco A of HVAC Hanger 2070 by plug welding with the omission of backing material, without establishing a new procedure by qualification.

t Response:-

a) Corrective steps which have been taken and results achieved:

Nonconformance Report (NCR) #1SN 14786 MW has been generated to document the identified concern and to provide appropriate' controls to assure satisfactory resolution. The NCR requires an evaluation of the

~

acceptability of the affected material as well as an investigation into the extent of the identified-concern.

'b) Corrective steps which will be taken to avoid further violations:

- Daniel is currently retraining craft supervision in the proper-use of welding technique N-1-1-A-18.

In addition, the Daniel. Project Welding Engineer will initiate a letter that will emphasize the importance of contacting Welding Superintendents or Welding Engineering when questions arise concerning welding or the use of welding techniques.

1

=

. ~.

f $.> *

  • Mr. J.E. Gagliardo KMLNRC'83-166 December 22, 1983 Response'(continued):

+

c) Date when full compliance will be achieved:

+

.The actions discussed in Paragraph b) of the response will be completed by December 30, 1983.

Supporting documentation for the responses provided above is available for review at the Wolf Creek job site.

If,you have any further questions concerning this response, please contact me or Mr. Otto Maynard of my staff.

.Yours very truly, 4^

M Glenn L. Koester Vice President - Nuclear GLK:bb' cc: SSchum d