Notice of Consideration of Issuance of Amend to License DPR-51 & Proposed NSHC Determination & Opportunity for Hearing.Amend Proposes Changes to TS to Address Installation of Battery Chargers on Each Vital Power Train
ML20080E782
Person / Time
Site: Arkansas Nuclear 
Issue date: 01/10/1995
From: Alexion T
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20080E785 List:
References
NUDOCS 9501180276
Download: ML20080E782 (8)


Text

..

7590-01 i

[

UNITED STATES NUCLEAR REGULATORY COMISSION t

ENTERGY OPERATIONS.'INC.

t t

DOCKET NO. 50-313 NOTICE OF CONSIDERATION OF ISSUANCE OF ANENDNENT To E

FACILITY OPERATING LICENSE. PROPOSED NO SIGNIFICANT HAZARDS CONSIDERATION DETERMINATION. AND OPPORTUNITY FOR A HEARING The U.S. Nuclear Regulatory Comission (the Commission) is considering issuance of an amendment to Facility Operating License No. DPR-51 issued to Entergy Operations, Inc. (the licensee) for operation of Arkansas Nuclear One, Unit I located in Pope County, Arkansas.

The proposed amendment revised technical specifications to address the installation of two battery chargers on each vital 125 yde power train in lieu of the " swing" battery charger that is currently used.

Before issuance of the proposed license amendment, the Comission will have made findings required by the Atomic Energy Act of 1954, as amended (the Act) and the Comission's regulations.

l The Comission has made a proposed determination that the amendment 1

request involves no significant hazards consideration. Under the Comission's regulations in 10 CFR 50.92, this means that operation of the facility in accordance with the proposed amendment would not (1) involve a significant increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a new or different kind of accident from any accident previously evaluated; or (3) involve a 9501180276 950110 DR ADOCK 0 33

significant reduction in a margin of safety. As required by 10 CFR 50.91(a), the licensee has provided its analysis of the issue of no significant hazards consideration, which is presented below:

Criterion 1 - Does Not Involve a Significant Increase in the Probability or Consequences of an Accident Previously Evaluated.

The vital 125 vde system is not an accident initiator.

It serves as a power supply to systems which mitigate the effects of postulated accidents.

The proposed Technical Specification (TS) changes are consistent with those of the plant system currently addressed by the TSs. The proposed Limiting Condition for Operation maintains the minimum equipment operability requirement of one battery charger per electrical train. The Action Statement allows operation for_ an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period with no operable battery charger on one electrical train, maintaining the current requirements. The separate requirement for testing a " swing" battery charger has been deleted. The remaining surveillance requirement wording continues to require testing and loading of all battery chargers on their associated busses, including the " swing" battery charger. These changes are considered to be purely administrative in nature as the requirements themselves have not been reduced.

The change to Specification 3.7.1.B is considered to be administrative in nature and results in consistency between the Limiting Condition for Operation and the associated Action Statement.

Therefore, the change does not involve a significant increase in the probability or consequences of any accident previously evaluated.

Criterion 2 - Does Not Create the Possibility of a New or Different Kind of Accident from any Previously Evaluated.

The proposed Technical Specification (TS) changes are consistent with those of the plant system currently addressed by the TSs. The proposed Limiting Condition for Operation maintains the minimum equipment operability requirement of one battery charger per electrical train. The Action Statement allows operation for an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period with no operable battery charger on one electrical train, maintaining the current requirements. The separate requirement for testing a " swing" battery charger has been deleted. The remaining surveillance requirement wording continues to require testing and loading of all battery chargers on their associated busses, including the " swing" battery charger. These changes are considered to be purely administrative in nature as the requirements themselves have not been reduced.

i

a

-3 The change to Specification 3.7.1.B is considered to be administrative in nature and results in consistency between the Limiting Condition for Operation and the associated Ac', ion Statement.

I Therefore, this change does agi create the possibility of a new or different kind of accident from any previously evaluated.

Criterion 3 - Does Not Involve a Significant Reduction in the Margin of Safety.

The proposed Technical Specification (TS) changes are consistent with those of the plant system currently addressed by the TSs. The proposed Limiting Condition for Operation maintains the minimum equipment operability requirement of one battery charger per electrical train. The Action Statement allows operation for an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> period with no operable battery charger on one electrical train, maintaining the current requirements. The separate requirement for testing a " swing" battery charger has been deleted. The remaining i

surveillance requirement wording continues to require testing and loading of all battery chargers on their associated busses, including i

the " swing" battery charger. These changes are considered to be purely administrative in nature as the requirements themselves have I

not been reduced.

i The change to Specification 3.7.1.B is considered to be administrative in nature and results in consistency between the Limiting Condition i

for Operation and the associated Action Statement.

Therefore, this change does D91 involve a significant reduction in the i

margin of safety, i

The NRC staff has reviewed the licensee's analysis and, based on this I

review, it appears that the three standards of 10 CFR 50.92(c) are satisfied. Therefore, the NRC staff proposes to determine that the amendment request involves no significant hazards consideration.

The Commission is seeking public comments on this proposed determination. Any comments received within 30 days after the date of publication of this notice will be considered in making any final determination.

Normally, the Commission will not issue the amendment until the expiration of the 30-day notice period. However, should circumstances change during the notice period such that failure to act in a timely way

p.

j

- l i

would result, for example,-in derating or shutdown of the facility, the q

Commission may issue the license amendment before the expiration of the 1

30-day notice period, provided that its final determination is that the

}

amendment involves no significant hazards consideration. The final

]

determination will consider all public and State comments received. Should

'l the Commission take this action, it will publish in the FEDERAL REGISTER a i

notice of issuance and provide for opportunity for a hearing after issuance. The Commission expects that the need to take this action will occur very infrequently.

Written comments may be submitted by mail to the Rules Review and l

Directives Branch, Division of Freedom of Information and Publications i

Services, Office of Administration, U.S. Nuclear Regulatory Commission,.

Washington, DC 20555, and should cite the publication date and page number of this FEDERAL REGISTER notice. Written comments may also be delivered to i

Room 6D22, Two White Flint North,11545 Rockville Pike, Rockville, j

i Maryland, from 7:30 a.m. to 4:15 p.m. Federal workdays. Copies of written i

comments received may be examined at the NRC Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC.

1 The filing of requests for hearing and petitions for leave to j

intervene is discussed below.

By February 16, 1995, the licensee may file a request.for a hearing with respect to issuance of the amendment to the subject facility operating license and any person whose interest may be affected by this proceeding and who wishes to participate as a party in the proceeding must file a written request for a hearing and a petition for leave to intervene.

Requests for a hearing and a petition for leave to intervene shall be filed

I t i 7'

in accordance with the Commission's " Rules of Practice for Domestic

)

Licensing Proceedings" in 10 CFR Part 2.

Interested persons should consult a current copy of 10 CFR 2.714 which is available at the Commission's i

Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, f

DC, and at the local public document room located at the Tomlinson Library, Arkansas Tech University, Russellville, Arkansas 72801.

If a request for a hearing or petition for leave to intervene is filed by the above date, the

{

Commission or an Atomic Safety and Licensing Board, designated by the

' Commission or by the Chairman of the Atomic Safety and Licensing Board i

Panel, will rule on the request and/or petition; and the Secretary or the designated Atomic Safety and Licensing Board will issue a notice of hearing i

or an appropriate order.

l As required by 10 CFR 2.714, a petition for leave to intervene shall i

set forth with particularity the interest of the petitioner in the proceeding, and how that interest may be affected by the results of the proceeding. The petition should specifically explain.the reasons why intervention should be permitted with particular reference to the following factors:

(1) the nature of the petitioner's right under the Act to be made party to the proceeding; (2) the nature and extent of the petitioner's property, financial, or other interest in the proceeding; and (3) the possible effect of any order which may be entered in the proceeding on the petitioner's interest. The petition should also identify the specific aspect (s) of the subject matter of the proceeding as to which petitioner wishes to intervene. Any person who has filed a petittoa for leave to intervene or who has been admitted as a party may amend the petition without requesting leave of the Board up to 15 days prior to the first

~

t

( :

prehearing conference scheduled in the proceeding, but-such an amended t

petition must satisfy the specificity requirements described above.

Not later than 15 days prior to the first prehearing conference scheduled in the proceeding, a petitioner shall file a supplement to the petition to intervene which must include a list of the contentions which are sought to be litigated in the matter. Each contention must consist of a specific statement of the issue of law or fact to be raised or controverted.

In addition, the petitioner shall provide a brief explanation of the bases of the contention and a concise statement of the alleged facts or expert opinion which support the contention and on which the petitioner intends to rely in proving the contention at the hearing.

The petitioner must also provide references to those specific sources and documents of which the petitioner is aware and on which the petitioner intends to rely to establish those facts or expert opinion.

Petitioner must provide sufficient information to show that a genuine dispute exists 1

with the applicant on a material issue of law or fact. Contentions shall j

be limited to matters within the scope of the amendment under I

consideration. The contention must be one which, if proven, would entitle the petitioner to relief. A petitioner who fails to file such a supplement which satisfies these requirements with respect to at least one contention will not be permitted to participate as a party.

Those permitted to intervene become parties to the proceeding, subject to any limitations in the order granting leave to intervene, and have the opportunity to, participate fully in the conduct of the hearing, including the opportunity to present evidence and cross-examine witnesses.

. c If a hearing is requested, the Commission will make a final determination on the issue of no significant hazards consideration. The final determination will serve to decide when the hearing is held.

If the final determination is that the amendment request involves no significant hazards consideration, the Commission may issue the amendment and make it immediately effective, notwithstanding the request for a hearing. Any hearing held would take place after issuance of the amendment.

If the final determination is that the amendment request involves a significant hazards consideration, any hearing held would take place before the issuance of any amendment.

A request for a hearing or a petition for leave to intervene must be filed with the Secretary of the Commission, U.S. Nuclear Regulatory Commission, Washington, DC 20555, Attention: Docketing and Services Branch, or may be delivered to the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC, by the above date.

Where petitions are filed during the last 10 days of the notice period, it is requested that the petitioner promptly so inform the Commission by a toll-free telephone call to Western Union at 1-(800) 248-5100 (in Missouri 1-(800)342-6700). The Western Union operator should be given Datagram Identification Number N1023 and the following message addressed to William D. Beckner: petitioner's name and telephone number, date petition was mailed, plant name, and publication date and page number of this FEDERAL REGISTER notice. A copy of the petition should also be sent to the Office of the General Counsel, U.S. Nuclear Regulatory Commission,

Washington, DC 20555, and to Mr. Nicholas S. Reynolds, Winston & Strawn, 1400 L Street, NW., Washington, DC 20005-3502, attorney for the licensee.

Montimely filings of petitions for leave to intervene, amended l

petitions, supplemental petitions and/or requests for hearing will not be entertained absent a determination by the Commission, the presiding officer or the presiding Atomic Safety and Licensing Board that the petition and/or request should be granted based upon a balancing of the factors specified in 10 CFR 2.714(a)(1)(1)-(v) and 2.714(d).

For further details with respect to this action, see.the application for amendment dated August 30, 1994, which is available for public inspection at the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC, and at the local public document room located at the the Tomlinson Library, Arkansas Tech University, Russellville, Arkansas 72801.

Dated at Rockville, Maryland, this 10th day of January 1995.

FOR THE NUCLEAR REGULATORY C0t911SSION v

Thomas W. Alexion, Projeg Manager Project Directorate IV-1 Division of Reactor Projects - III/IV Office of Nuclear Reactor Regulation

.