Malling Address c/,

Allbam2 Power Company 600 North 18th Street Post Offica Box 2641

.,2 '.

Birmingham, Alabama 35291 7

Telephone 205 783-6081 F. L Clayton, Jr.

E @ % T o*"'

M il " 2 Pl2 : 2 9 AlabamaPbwer theSouthem electnc system January 30, 1984 Docket No. 50-348 Docket No. 50-364 Mr. J. P. O'Reilly U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, N.W.

Suite 3100 Atlanta, Georgia 30303 4

SUBJECTi J. M. Farley Nuclear Plant Special Report - Unit 1 and Unit 2 RE:

Technical Specification 3.3.3.1

Dear Mr. O'Reilly:

This special report is being submitted in accordance with Unit 1 and Unit 2 Technical Specification 3.3.3.1 action statement 27A.

At 0800 on 1/12/84 and 0800 on 1/14/84, during performance of FNP-1-STP-814/FNP-2-STP-814 (Plant Vent Stack Effluent Monitor (R-298) Radiological Calibration), Unit 1 radiation monitor R-29B (Plant Vent Stack Effluent Mcni-tor) and Unit 2 radiation monitor R-29B, respectively, were declared inoperable when it was determined that four of the nine detectors on each monitor had failed. Although nonc of the failed detectors are required by Technical Speci-fications, their replacement required that both monitors be removed from ser-vice for longer than seventy-two hours.

While these monitors were removed from service, an alternate monitoring method, as required by Unit 1 and Unit 2 Technical Specification 3.3.3.1 action statement 27A, was implemented in accordance with established plant procedures.

The failed detectors were replaced and following satisfactory completion of FNP-1-STP-814/FNP-2-STP-814, Unit 1 radiation monitor R-29B and Unit 2 radiction monitor R-29B were restored to operable status at 1510 on 1/21/84.

Y urs ry tr y,

W D%p

/pF. L. Clayton, Jr.

s l

FLCJr/KWM:bhj e

id2Z 8402060360 840130 PDR ADOCK 05000348 lp s

PDR

,.,,