Interim Deficiency Rept Re Accident Temp Effects on Containment Level Measurements.Design Being Revised for Class IE Steam Generator Level Issued Measurements.Next Rept by 840420
ML20080A572
Person / Time
Site: Midland
Issue date: 01/27/1984
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
26673, 82-05-7, 82-5-7, NUDOCS 8402060124
Download: ML20080A572 (3)


Text

.

consumers Power Company "l"" ",u'** _,,.j,,,,. r.,,.,,,,,

and Con,truction

~

Generet offices: 1945 West Pernell Road, Jackson, MI 49201 e (517) 788-0453 January 27, 1984 82-05 #7 50 -3391 50-3 SD Mr J G Keppler, Regional Administrator US Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND ENERGY CENTER PROJECT -

DOCKET NOS 50-329 AND 50-330

. ACCIDENT TEMPERATURE EFFECTS ON CONTAINMENT LEVEL MEASUREMENT FILE:

0.4.9.61 SERIAL: 26673

Reference:

J W Cook letters to J G Keppler, same subject:

1) Serial 16192, dated May 14, 1982
2) Serial 19053, dated September 28, 1982
3) Serial 10689, dated February 1, 1983
4) Serial 22188, dated May 6, 1983
5) Serial 23783, dated August 31, 1983
6) Serial 26575, dated October 31, 1983 This letter, as were the referenced letters, is an interim 10CFR50.55(e)

. report _concerning accident temperature effects on level measurements inside containment.

Investigation of this condition has determined that the design must be revised for Class 1E steam generator level measurements. The following design changes are being made:

1) Addition of one Class IE level transmitter per steam generator.
2) Rearrangement of the wide-range Class 1E level transmitters. 3) Addition of temperature monitoring on reference legs of two Class 1E level transmitters per steam generator.

4)

Insulation of Class IE level transmitter reference Icgs.

8402060124 840127 PDR ADOCK 05000329 S

PDR

~T t 1 OC0184-0038A-MP01 pE.B r20 t/

I T

t 2

Serial 26673 82-05 #7

~

Level transmitter installation design drawings have been issued for

. construction. In addition, Consumers Power Company is preparing a formal response.to NRC Question 031.54 and the associated IE Bulletin.

Consumers Power Company will provide another status report, interim or final, by April 20, 1984.

JWC/WRB/AHB/cd CC: RJCook, NRC Resident Inspector Document Control Desk, NRC Midland Nuclear Plant Washington, DC DSHood, NRC Office of NRR INPO Records Center OC0184-0038A-MP01

/

f 3

Serial 26673 82-05 #7 OM/0L SERVICE LIST Mr Frank J Kelley Atomic Safety & Licensing Attorney General of the Appeal Board State of Michigan U S Nuclear Regulatory Commission Ms Carole Steinberg, Esq Washington, DC 20555 Assistant Attorney General Environmental Protection Division Mr C R Stephens (3) 720 Law Building Chief, Docketing & Services Lansing, MI 48913 U S Nuclear Regulatory Commission Office of the Secretary Washington, DC 20555 Mr Myron M Cherry, Esq Suite 3700 Ms Mary Sinclair Three First National Plaza 5711 Summerset Street Chicago, IL 60602 Midland, MI 48640 Mr Wendell H Marshall Mr William D Paton, Esq RFD 10 Counsel for the NRC Staff Midland, MI 48640 U S Nuclear Regulatory Commission Washington, DC 20555 Mr Charles Bechhoefer, Esq.

Atomic Safety & Licensing Atomic Safety & Licensing Board Panel Board Panel U S Nuclear Regulatory Commission U S Nuclear Regulatory Commission Washington, DC 20555 Washington, DC 20555 Dr Frederick P Cowan Ms Barbara Stamiris 6152 N Verde Trail 5795 North River Road Apt B-125 Rt 3 Boca Raton, FL 33433 Freeland, MI 48623 Mr Fred C Williams Dr Jerry Harbour Isham, Lincoln & Beale Atomic Safety & Licensing 1120 Connecticut Ave NW, Suite 325 Board Panel Washington, DC 20036 U S Nuclear Regulatory Commission Washington, DC 20555 Mr James E Brunner, Esq Mr M I Miller, Esq Consumers Power Company Isham, Lincoln & Beale 212 West Michigan Avenue Three First National Plaza Jackson, MI 49201 52nd Floor Chicago, IL 60602 Mr D F Judd Mr John Demeester, Esq Babcock & Wilcox Dow Chemical Building PO Box 1260 Michigan Division Lynchburg, VA 24505 Midland, MI 48640 Mr Steve Gadler, Esq Ms Lynne Bernebei 2120 Carter Avenue Government Accountability Project St Paul, MN 55108 1901 Q Street, NW Washington, DC 20009 September 6, 1983 OC0184-0038A-MP01