Forwards Degraded Grid Voltage Test Voltage Analysis Tabulation,Per Util ,In Response to NRC Transmitting Amend 52.All Test Values Are Above Analytical Values Indicating Analysis Conservative
ML20079S199
Person / Time
Site: Davis Besse 
Issue date: 01/23/1984
From: Crouse R
TOLEDO EDISON CO.
To: Stolz J
Office of Nuclear Reactor Regulation
References
1022, TAC-51738, NUDOCS 8402030242
Download: ML20079S199 (2)


Text

c. -

.o 5

-[

TOLEDO

%me EDISON Docket No. 50-346 nCHARO P. CROUSE License No. NPF-3 m msm

-Serial No. 1022

. January 23, 1984 Director of Nuclear Reactor Regulation Attention:

Mr. John F. Stolz Operating Reactor branch No. 4 Division of Operating Reactors United States Nuclear Regulatory Commission Washington, D.C. 20555

Dear Mr. Stolz:

This letter is to conclude our response to your letter dated February 17, 1983 (Log No. 1218), transmitting Amendment 52 which requested Toledo Edison to verify, by tests, the voltage analysis of the Davis-Besse Nuclear Power Station, Unit 1.

In our letter, dated March 23, 1983 (Serial No. 925), we submitted the schedule and test outline for the tests. By this letter we are providing the conclusion based on the test results.

A comparison of the test data with the analytical results calculated from the actual testing conditionslindicated that all test values are above the analytical values indicating the analysis to be on the conservative side.

Very truly yours, ff m

RPC:LCS:MAK cj a/16 cc: DB-1 NRC Resident Inspector

[

O THE TOLCOO EDISON COMPANY EDISON FLAZA 300 MAOISON AVENUE TOLEDO, OHIO 43652 l

. DECRADED CRID VOLTACE TEST VOLTACE ANALYSIS TABUIATION STEADY STATE VOLTAGE VALUES TRANSIElff VOLTACE VALUES BUS TEST ANALYTICAL

  • DIFFrarur' RCP START CONDEllSATE Ptar START (VOLTS)

TEST AllALYTICAL DIFTERDICE TEST ANALYTICAL DIFFERENCE

'J' 342 342 0

342 342 0

342 342 0

(345tV)

'A' 14 13.67 2.41 12.5 12.17 2.7E 13.9 13.20 5.22 (13.BEV)

ABOVE A80VE ABOVE C1 4.25-4.18 1.72 3.81 3.71 2.72 3.9 3.83 1.8E (4.16KV)

ABOVE ABOVE ABOVE C2 4.28 4.18 2.4%

3.84 3.71 3.51 4.0 3.83 4.'I (4.16KV)

ABOVE ABOVE ABOVE El 485 470.8 3.0%

445 414.9 7.31 457 428.5 6.71 (480)

ABOVE A30yg ABME TEl 12 8. 1 117.2 9.33 115.6 103.2 121 120.6 106.6 13.11 (120V)

ABOVE ABOVE A30VE

  • DI m RENCE =

VA x100 =

2 ABOVE OR BEIDW ME ANALYTICAL VALUE k

WHERE VT =

VOLTACE VALUE, TEST VA =

VOLTAGE VALUE. ANALYTICAL

  • %