ML20079J652

From kanterella
Jump to navigation Jump to search
Advises That Onsite Radiograph Sets of Piping Subassemblies Supplied by ITT-Grinnell Reviewed,In Response to IE Bulletin 82-01,Revision 1,Suppl 1.Two Subassemblies Rejected.Results of Investigation Will Be Provided by 830201
ML20079J652
Person / Time
Site: Marble Hill
Issue date: 12/16/1982
From: Shields S
PSI ENERGY, INC. A/K/A PUBLIC SERVICE CO. OF INDIANA
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-SSINS-6820 IEB-82-01, IEB-82-1, SVP-0058-82, SVP-58-82, NUDOCS 8212280304
Download: ML20079J652 (2)


Text

.

PUBLIC SERVICE INDIANA S. W. Shields senior vice President.

December 16, 1982 Nuclaar Division SVP-0058-82 Mr. James G. Keppler, Docket Nos.: STN 50-546 Regional Administrator STN 50-547 U. S. Nuclear Regulatory Commission Construction Permit Nos.:

Region III CPPR - 170 799 Roosevelt Road CPPR - 171 Glen Ellyn, Illinois 60137 Marble Hill Nuclear Generating Station - Units 1 and 2 IE Bulletin No. 82-01, Rev. 1, Supplement 1

Dear Mr. Keppler:

In response to the subject Bulletin, Public Service Company of Indiana, Inc. (PSI) has reviewed onsite radiograph sets of piping subassemblies supplied by ITT Grinnell, Kernersville, North Carolina. This encompassed a 100 percent review of the onsite radiograph sets for welds in shop fabricated ASME Code Class 1 and 2 piping subassemblies, regardless of wall thickness. The review resulted in the inspection of 69,048 radiographs with the applicable ASME Code penetrameter sensitivity being determined to have been altered on 129 of them. Of these 129 altered radiographs, acceptable weld quality on ninety-five (95) of them was demonstrated based on the equivalent or higher penetrameter sensitivity being discernible on the film or verifying the acceptability of a duplicate film. The remaining thirty-four (34) radiographs represented thirteen (13) welds on ten (10) piping subassemblies. Weld quality was demonstrated acceptable on eight (8) of these piping subassemblies by having radiography again performed on the welds in question and finding the resulting radio-graphs acceptable. The two (2) remaining piping subassemblies were rejected due to part geometry interfering with radiography of the welds.

For radiographs received after this review, Quality Assurance checklist attributes have been revised to include verification that the penetra-meter image shows no evidence of enhancement of the essential T-hole.

The possibility of ITT Grinnell, Kernersville, North Carolina, providing shop fabricated ASME Code Class 1 and 2 piping subassemblies with pipe wall thicknesses less than one half inch to other PSI suppliers is still being investigated. A final response containing the results of this 8212290304 821216 PDR ADOCK 05000546 G

PDR DEC 2 01982 P. O. Box 190, New Washington, Indiana 47162 812. 289.3000

D PUBUC SERVICE INGANA Letter:

J. G. Keppler December 16, 1982 SVP-0058-82 investigation will be filed on or before February 1, 1983.

If you have any questions regarding this matter, please contact me at your convenience.

PUBLIC SERVICE COMPANY OF INDIANA, INC.

By '

S. W. Shields Senior Vice President-Nuclear Division STATE OF INDIANA

)

) SS:

COUNTY OF JEFFERSON )

Subscribed and sworn to before me, a Notary Public, in and for said County and State, this 16th day of December, 1982.

M/[

obd7 w

( (/

/

) ' Notary Public My Commission Expires:

/2 -/d - ((

My County of Residence:

cbhbu VH SWS/LGY/bak cc: Director, Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.

20555 J. E. Konklin J. J. Harrison