Text
123 Man Street no Whte Rains. New York 10601 314 681.6200
- > NewWrkPbwer g "::tt,
& Authority
~ *- o--e-January 18, 1984 JPN-84-01 Director of Nuclear Reactor Regulation U.S.
Nuclear Regulatory Commission Washington, D.C.
20555 Attention:
Mr. Domenic B. Vassallo, Chief Operating Reactors Branch No. 2 Division of Licensing
Subject:
James A.
FitzPatrick Nuclear Power Plant Docket No. 50-333 Diesel Generator Fast Cold Starts
Reference:
1.
G.
Eisenhut to All Licensees of Operating Reactors, dated December 16, 1983.
Dear Sir:
The table below indicates the data for fast cold starts for the diesel generators from 12/1/82 to 12/1/83.
Scoring has been seen in some cylinder walls and upper valve train components during refueling outage maintenance.
These indications have not caused any forced outages to date.
The long-term impact on reliability and availability has not been quantified but is known to be negative.
Diesel Pairs Reason for Start A&C B&D Surveillance Testing 36 25 scheduled & for inop. equipment surveillance tests Maintenance (each refueling outage) approx. 4 per overhaul Actual Demands approx. 1 per cycle 8401230255 840118 DR ADOCK 05000333
\\#
PDR Q
.n
't
.o If you have any further questions, please contact Mr. J.
A. Gray, Jr. of my staff.
-Very truly yours,
[
, V Executive Vice President Nuclear Generation cc:
Office of the Resident Inspector U.
S. Nuclear Regulatory' Commission P. O. Box 136 Lycoming,_NY 13093 j '
4 i
j',
4 a
,,-,-,,,----,------..--r-
- - -,.. - - - - - - - -,,, - - - - -.. -, - -,