Suppls 800730 Response to IE Bulletin 80-16, Potential Misapplication of Rosemount,Inc Model 1151 & 1152 Pressure Transmitters W/Either a or D Output Codes. Existing Instruments to Be Upgraded W/Type N Circuit Boards
ML20078D203
Person / Time
Site: Surry  
Issue date: 09/16/1983
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-SSINS-6820 516, IEB-80-16, NUDOCS 8310040450
Download: ML20078D203 (5)


Text

,

ne.

-,~

VIRGINIA ELECTHIC AND Po5ER' MPANY 1

iA

..:.0 F:G I A RicimoNo,VrnorNIA 21 1

83 SEP23 P 5: 20 w.1.. s --

y, d*",$",'***',,,,,

September 16, 1983 Mr. James P. O'Reilly Serial No. 516 Regional Administrator N0/WDC:cfm Region.II Docket Nos. 50-280 U. S. Nuclear Regulatcry Commission 50-281 101 Marietta_ Street, Suite 2900 License Nos. DPR-32 Atlanta, Georgia-30303 DPR-37

Dear Mr. O'Reilly:

j SUPPLEMENTAL RESPONSE TO IE BULLETIN 80-16 SURRY POWER STATION In NUREG/CR-3047, " Closeout of IE Bulletin 80-16: Potential Mis-application of Rosemount Pressure Transmitters", Surry Power Station is listed with an "open" status. This letter is to closeout this issue for Surry.

In our response to IE Bulletin 80-16, " Potential Misapplication of Rosemount Inc. Models 1151 and 1152 Pressure Transmitters With Either

'A' or 'D' Output Codes", dated July 30, 1980, we stated that Model 1152 pressure transmitters were installed and provided the data requested for each instru:nent.

We further stated that with regard to Surry Power Station Units 1 and 2, no corrective action was planned, that an anal-ysis was ongoing concerning the ' range of process variable measured for

-accident conditions, and that any results.of the analysis showing infor-mation contrary to our findings would be forwarded as a supplement to the original submittal.

While the analysis has sown no information contrary to the original findings,-it has been decided to upgrade the existing instruments either

- through replacement of the instrument or installation of Type "N" re-placement circuit boards. This action has been completed for Unit 2 and will be accomplished in Unit'l during a future outage.

A current status of installed Rosemount Inc. Model 1151 and 1152 pres-sure transmitters (that. do not fall under environmental qualification requirements) with output codes "A" or "D" in safety related systems is attached.

Very truly y urs,

/

ny W. L. Stewart Attachment B310040450 830916 ll

??"

?!L -

r.,..

.VImOIMIA Es.scTasc Ano Powra COMPANY TO James

~P.

O'Reilly 2

cc: Mr. Steven A. Varga, Chief

.Uperating Reactors Branch No. 1 Division of Licensing Mr. ' D. J. Burke NRC Resident Inspector Surry. Power Station 4

i 4

i i

1 1

1 l

i

+

l i

k 5

Surry Power Station Response to IE Bulletin 80-16 A.

Model No:

1152 DP4A92PB Serial No.

69970 B.

Range Limits:

0-150" H O 2

C.

Range Settings: 0-25" H O 2

~ '

D.

Range of Process Variable Measured for Normal Conditions:

0-25" H O = 4-20 ma OUT.

2 Accident Conditions:

14" E.

Values of Process Variable which could Produce Anomalous Indication: 210" H O 2

F.

Service / Function: TK B accumulator level A.

Model No:

1152 DP4A92PB Serial No.

52214 B.

Range Limits: 0-150" H O 2

C.

Range. Settings: 0-25" H O 2

D.

Range of Process Variable Measured for Normal Conditions:

0-25" H O = 4-20 ma OUT.

2 Accident Conditions:

14" E.

Values of Process Variable which could Produce Anomalous Indication: 210" H O 2

F.

Service / Function: Accumulator TK B level A.

Model No:

1152 DP4A92PB Serial No.

120017 B.

Range Limits:

0-150" H O 2

C.

Range Settings:

0-25" H O 2

D.

Range of Process Variable Measured for Normal Cunditions:

0-25" H O = 4-20 ma OUT.

2 Accident Conditions:

14" E.

ValueF of Process Variable which could Produce Anomalous Indication: 210" H O 2

F.

Service / Function: Accumulator TK C level L

~


_------.----.;--y;

-m A.

Model No:

1152 DP4A92PB Serial No.

386089 B.

Range Limits:

0-150" H O 2

C.

Range Settings:

0-25" H O 2

D.

Range of Process Variable Measured for Normal Conditions:

0-25" H O = 4-20 ma OUT.

2 Accident Conditions:

14"

~.

E.

Values of Process Variable which could Produce Anomalus Indication: 210" H O 2

F.

Service / Function: TK A accumulator level A.

Model No:.1152 DP4A92PB Serial No.

52543 B.

Range Limits:

0-150" H O 2

C.

Range. Settings:

0-25" H O 2

D.

Range of Process Variable Measured for Normal Conditions:

0-25" H O = 4-20 ma OUT.

2 Accident Conditions: 14" E.

Values'of Process Variable which could Produce Anomalous Indication: 210" H O 2

F-Service / Function: TK A accumulator level r

A.

Model No:

1152 DP4A22DP Serial No.

48968 B.

Range Limits:

0-150" H O 2

C.

Range Settings:

0-48" H O 2

D.

Range of Process Variable Measured for Normal Conditions: 0-48" H O = 4-20 ma OUT.

2

-Accident Conditions: 48" E.

Values of Process Variable which could Produce Anomalous Indication: 210" H O 2

F.

Service / Function: Primary Drains Transfer TK Level

A.

Model No.-

1152 DP4A92PB Serial No.

52217 B.

Range Limits: 0-150" H O

~

2 C.

Range Settings:

0-25" H O 2

D.

Range of Prccess Variable Measured for Normal Conditions:

0-25" H O = 4-20 ma OUT.

2

' Accident Conditions:

14" E.

Values of Process Variable which could Produce Anomalous Indication: 210" H O 2

F.

Service / Function: Accumulator TK C Level l