August 7,1991
{
Docket Nos. 50-348 50-364 U. S. Nuclear Regulatory Commission L
Attention: Document Control Desk l
l Washington,-D. C. 20555 Joseph M. Farley Nuclear Plant inoperable Fire Protection Water Storage Tanks 24-Hour Report Gentlemen:
't in accordance with-Technical 5)ecification 3.7.ll.l.b, a 24-hour tele) hone notification was provided to tie NRC on August 7, 1991, regarding bot 1 fire protection water storage' tanks decreasing below their technical specification minimum level. This letter serves as confirmation of the above notification.
On August 6,1991 at 9:30 p.m., a valve in the fire protection-supply header to the Unit 2 cooling towers inadvertently opened causing the level in both fire protection water storage tanks'to decrease below the required technical i
specification minimum. The subject sup)1y header valve was isolated and the tanks were replenished to above the tecinical specification minimum level within one hour, t
E A Special Report will be submitted to the NRC within 14 days.