Hew Hampshire Ted C. Feigenbaum h

Pret,ident and Ch;ef Exewtive Ofhcer NYN 91105 July 3,1991 United States Nuclear Regulatory Commission Washington, DC 20555 Attention:

Document Control Desk

References:

(a)

Facility Operating License No. NPF-86, Docket No. 50 443.

(b)

Transcribed Public Meeting Hetween New Hampshire Yankee and the NRC conducted on April 10, 1991.

(c)

NilY Letter NYN-91076 dated hiay 13, 1991, 'Tr a n s mit t al of the Program Description for the Reverification of Pullman liiggins Field Weld Records", T. C. Feigenbaum to T. T. Martin.

Subject:

Report of Weld Record Anomaly For Field Weld 1-CBS 1201-07-F0701 Gentlemen:

In the April 10,1991 Public Meeting between New llampshire Yankee (NilY) and the NRC (Reference (b)], and as provided in the N11Y Program Description for the Reverification of Pullman liiggins Field Weld Records, transmitted to the NRC on May 13, 1991 l Reference (c)], NiiY agreed to provide the NRC with a written report of any weld record anomalies within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of the determination that a report is required.

A c cor din gi,s, enclosed please find a " Report of Weld Records Anomaly for Field Weld 1-CBS 1201-07 F0701*

This report relates to a record anomaly which NHY determined on July 2,19f 1, was reportable pursuant to the program description. Subsequent to discussions with Region I personnel, NHY is submitting the Justification for Continued Operation for the recorc anomaly in this letter.

As provided in Enclesure 1, the Radiographic inspection Report and associated radiographs for Pullman-Higgins Field Weld 1 CBS 1201-07-F0701 has not yet been located and may be misfiled or inadvertently discarded. Other quality documentation demonstrates that an acceptable weld was installed, radiographed, and reviewed by the required, qualified personnel. NHY has evaluated this records anomaly and has deterrnined that it do,

'ot adversely affect or call into question the physical quality of weld 1-CllS-120107-F07t,,

or other Seabrook Station welds.

In order to correct the record anomaly, this weld will be re-radiographed during the 1991 Seabrook refueling outage, the film will be reviewed in accordance with our present program reouirements, and the film will be placed ir. the records vault to complete th required quality document set. The Justification for Continued Operations for this anomaly contained in Enclosure 1 has been reviewed by the Station Operation Review Committee (SORC) and determined to be acceptable.

9107050263 910703

{DR ADOCK 05000443 l

PDR New Hampshire Yankee Division of Public Service Company of New Hampshire p0

~

~

P.O. Ib 300

  • Seabrook, NH 03874
  • Telephone (603) 474-9521 i

u

United States Nuclear Rs Sulatory Commission J uly 3,1991 -

Attention:

Document Control Desk Page two Should you have any questions regarding this matter, please contact hit. Neal A.

Pillsbury, Director of Quality Programs at (603) 474 9521, extension 33414 Very truly yours,

. f hp f-Ted C. Fe' nbaum TCP:J ES/act Enclosure cc:

Mr. Gordon E. Edison, Sr. Project Manager Project Directorate 13 Di'.it!on of Reactor Projects U.S. Nuclear Regulatory Commissior

-Washington, DC 20555 Mr. Ebc C. McCabe, Chief Reactor Projects Section -

U S Nuclear Regulatory Commission F. ion 1 4h, Allendale Road King of Prussia, PA 19406 Mr. Thomas T. Martin, Regional Administrator Region l' 475 Allendale Road King of Prussia, PA 19406 Mr. Kenneth E. Brockman Office of the Executive Director for Operations-U.S. Nuclear Regulatory Commission 11555 Rockville Pike Rockville, MD 20852 Mr. Noel Dudley NRC Senior Resident inspector P.O. Box 1149 Seabrook, NII 03814 Mr. Phil Joukoff United States Nuclear Regulatory Commissiori 1450 Maria Lane, Suite 210 Walnut Creek, CA 94596 Mr. Frank Forgione, Special Agent Office of the inspector General United States Nuclear Regulatory Commission MNBB 6715 Washington, DC 20555

- _.~.

-