OUKE POWER April 18, 1991 S.C. Department of Health and Environmental Control (DHEC)
Ground-Water Protection Division 2600 Bull Street Columbia, SC 29201 ATTENTION:
Mark Berenbrok
SUBJECT:
Catawba Nuclear Station Underground Storage Tanks File:
CN-707.20
Dear Mr. Berenbrok:
At Catawba Nuclear Station on April 15, 1991, a small amount of diesel fuel contamination was found while drilling a cathodic protection well.
You have requested the details of the corrective action already taken and future planned corrective action.
This information is attached.
If you have any questions about this, please contact me at (704) 373-2758.
J.
S. Carter, Technical System Manager Nuclear Environmental Compliance A
-Alan Nietering Nuclear Production Engineer
\\ARN Attachments 9106060063 910418 PDR ADOCK O*3000413
/
s PDR i
f g
vev
e' e
s Corrective Action Taken 1.
4/15/91 - Well drillers noticed diesel fuel odor in the fluid at the bottom of a cathodic protection well they had drilled.
They notify station compliance personnel.
2.
4/15/91 Station compliance personnel investigated the situation, looked at environmentcl regulations on this topic, and notified DHEC.
3.
4/15/91 - Plant personnel started monitoring diesel fuel level in the Unit 1 emergency diesel generator fuel tanks every three hours.
These tanks are located near the newly drilled well.
4.
4/15/91 - Groundwater monitoring wells near the newly drilled well were monitored for diesel fuel.
No diesel fuel detected in these wells via a snif f test.
These wells are monitored on a weekly basis and have not indicated any groundwater contamination.
5.
4/16/91 - Samples from groundwater monitoring wells near the newly drilled well were taken and visually inspected.
No diesel fuel is detected in these wells.
1
\\
I Corrective Action Planned the 4 die.s1 An Underground Tank Tester will integrity testfuel tanks loc This should 1.
be performed on 4/19/91 or shortly thereafter.
h well A groundwater monitoring well will be installed where t e well.
This drilled for the cathodic protectionto more thoroughly 2.
groundwater monitoring well will help usinvestigate the soil cont was l
_ - - _