Ro:On 830619,while Oa Diesel Fire Pump Running,Due to Frequent Autostart Signal on Low Pressure,Trouble Light Received.Caused by Broken V-belt.Pump Operability Restored on 830629
ML20077B087
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 07/15/1983
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8307220542
Download: ML20077B087 (1)


Text

m

!', c Ny) Commonwealth LaS:lla County Nuct:ar Station Edison RuralRoute #1 Box 220 v' / Marceilles, Illinois 61341

'G Telephone 81S/357-6761 ah

/J July 15, 1983 Mr. James G. Keppler

, Regional Administrator Directorate of Regulatory Operations, Region ill U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137

Dear Sir:

This report is submitted in accordance with LaSalle Unit 1 Operating License NPF-11, Appendix B, Technical Specifications 3.7.5.1 and 6.6.c.

On June 19,1983 at 0408, while OA Diesel Fire Pump (DFP) was running, because of frequent Auto start signal on low pressure, the OA DFP trouble light was received in the control room. When the OA DFP trouble light was investigated, the OA DFP was found to have a broken V-belt which stopped the engine cooling water flow and the engine over heated. As a resul t, the OA DFP was declared i nope rab l e .

The 08 DFP and service water back-up were operable at all times to supply the fi re protection system i f needed.

Operability was restored to the 0A DFP on June 29, 1983 at 2300 0A DFP was test run in accordance with LOS-FP-A2 and LOS-FP-W2 before operability was declared.

l 1 G J. Diederich Station Superintendent LaSalle County Station O