ML20076L648

From kanterella
Jump to navigation Jump to search
Ro:On 830811 & 12,during Insp,Nylon Pull Ropes Used for Cable Pulling Discovered Sealed Along W/Cables in Various CT Gypsum Fire Stops & Pipe Found Open Through Fire Wall. Ropes Removed & Pipe Sealed
ML20076L648
Person / Time
Site: LaSalle 
Issue date: 09/09/1983
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8309160187
Download: ML20076L648 (1)


Text

Commonwe:lth Edison LaSalle County Nuclear Station Rural Route #1, Box 220 Marseilles. Illinois 61341 Telephone 815/357-6761 September 9, 1983

, 3 - Tl )

James G. Keppler Regional Admini st rator Region 111 U.S. Nuc lear P,equlatory Conini ssion 799 RooseveIt Road Glen Ellyn, IL 60137

Dear Sir:

This Special Report is submi t ted in accordance wi th LaSalle Unit Operatinq License NPF-II, Appendix A, Technical Specifications 3.7.6 and 6.6.c.

On August 11 and 12, 1983, inspections were performed and it was discovered that nylon pull ropes, used for cable pulling, were sealed alona with adjacent cables in various CT Gypsum fire stops. These ropes were apparently in the risers / trays for future additional cable pulls. Also, a pipe was found open going throunh a fire wall.

Since fuel load, area fire detection has been operable and an hourly fire watch in this area has been in e f fect.

The nylon pull ropes for the barriers involved were removed and the penetra-tions vere satisfactorily sealed on August 16 and 23, 1983. The open pipe was also satisfactorily scaled on August 23, 1983.

G. J. Diederich h Superintendent

LaSalle County Station GJD/JSK/GW/rg Enclosure cc

Director of Inspection & Enforcement Director of Management Information & Program Cont rol U.S. NRC Documen t tianaaement B ranch INP0-Records Center File /NRC l

i 8309160187 830909 PDR ADOCK 05000373 4EP 121983 S

PDR ll4 wf