TELEX 802507 PSD-RYMO August 10, 1983 Nuclear Regulatory Commission Region II Office 101 Marietta St., NW Suite 3100 Atlanta, GA 30333 Attention:
J. D. O'Reilly, Regional Manager
Reference:
10'CFR21 - Report of Defect (PSD Report 10CFR21-0017)
Emergency Diesel Generator 2B-B Parsons-Peebles Electric Products, Inc. A.C.
Synchronous Generator S/N 14701228 Gentlemen:
With reference to our report 10CFR21-0017, we have now identified the following United States Nuclear Plants for which Power Systems furnished generators which are effected. The generators were supplied to these Nuclear Plants by the General Electric Company.
Allens Creek IWO 6017 Grand Gulf IWO 377 Skagit IWO 6004 Black Fox IWO 6016 Attached is a copy of our notification to the General Electric Company.
Very truly yours, POWER SYSTEMS A MORRISON-KNUDSEN DIVISION
~
Harry W. Falter, P.E.
Division Engineer l
HWF/voa Attachment cc: Murlin Grayson (M-K Boise)
W. Frank Jones (PSD)
Ed Martin (PSD)
COT @J Tom Iannuzzi (PSD) mgggL 8308190361 830810 D-J 6 PDR ADOCK 05000416 8
CREATORS OF ELECTRICAL POWER SUPPLY SYSTEMS Cs o POWERSYSTEMS A-
. N NUOMM OfVIG40N KV NT NORTH CA OuNA 27 1 Wlu'a'a%"" "" "'"
August 10, 1983 Serial No. 6017C-0 0158 Serial No. 377C-0-0231 Serial No. 6004C-0-0128 Serial No. 6016C-0-0165 General Electric Company 175 Curtner Avenue San Jose, CA 95125 Attention:
Mr. R. F. Pariani M/C 521
Reference:
Order No. 205-AG894, Allens Creek IWO 6017 Order No. 205-AD585, Grand Gulf IWO 377 Order No. 205-AG897, Skagit IWO 6004 Order No. 205-AG898, Black Fox IWO 6016 Gentlemen:
Parsons-Peebles/ Electric Products Division has notified Power Systems that a possible problem exists with the generator supplied under the above referenced purchase orders.
The problem was found to be wear of the generator shaft insulation material under the inner race of the cylindrical roller bearing. The wear allowed the shaft to drop down and rub the bearing inner and outer oil seals (bearing cover). The insulation wear was caused by the turning or slipping of the inner bearing race.
The generator manufacturer is presently studying the problem to determine whether a generic defect exists and what corrective action may be required.
We will advise you as soon as we receive the report.
Power Systems Division as well as TVA have notified the NRC in accordance with 10CFR21.
Very truly yours, POWER SYSTEMS A
SEN DIVISION Ed Martin Manager-Contracts EM/voa
-