ML20076A723

From kanterella
Jump to navigation Jump to search
Ro:On 830628,digital Metal Impact Monitoring Sys Reactor Vessel Lower Channel Declared Inoperable When Sensor 750 Could Not Render Channel Operable Since Failure on 830616. Cause Unknown
ML20076A723
Person / Time
Site: Summer 
Issue date: 08/03/1983
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8308180297
Download: ML20076A723 (2)


Text

w k,'

SOUTH CAROLINA ELECTRIC & GAS COMF@NKRgl..:

ATLA;

g'4'

,o. r o,..c. m.

COLuusiA. SouTM CAnoWNA 29218 h} fg O. W. DixoN. JR.

vice Pass.osNt sv e t... o,...,.c ~.

August 3, 1983 Mr. James P. O'Reilly Regional Administrator U.S. Nuclear Regulatory Commission Region II, Suite 2900 101 Marietta Street, N.W.

Atlanta, Georgia 30303

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report

Dear Mr. O'Reilly:

Please find attached a Special Report for Virgil C.

Summer Nuclear Station.

This Special Report la required by Technical Specification 6.9 2 as a result of entry into Action Statement (a) of Technical Spectrication 3 3.3.10, " Loose-Part Detection Instrumentation," on June 28, 1983 Should there be any questions, please call us at your convenience.

Very truly yo s,

/

0. W.

Dixon, Jr.

CJM:0WD/mac Attachment cc:

V. C. Summer C.

L.

Ligon (NSRC)

E. H.

Crews, Jr.

G.

J.

Braddick T. C.

Nichols, Jr.,/0. W. Dixon, Jr.

J.

C.

Miller E.

C.

Roberts J.

L. Skolds H. N. Cyrus J.

B.

Knotts, Jr.

Group / General Managers I&E (Washington)

O. S.

Bradham Document Management R.

B.

Clary Branch C.

A. Price INPO Records Center A. R.

Koon NPCF D.

A.

Lavigne File (Lic./Eng.)

J.

F.

Heilman 8308190297 830803 i

PDR ADoCK 05000 NFICIAE COPY p

f[AL ll

c-i r "

Mr. James P. O'Reilly Special Report Page Two August 3, 1983 CAUSE OF THE MALFUNCTION On June 28, 1983, with the Plant in Mode 1, the Reactor Vessel Lower Channel of the Digital Metal Impact Monitoring System (DMIMS) was declared inoperable when Sensor 751 failed a Channel Check.

Redundant Sensor 750 could not be selected at this time to return the channel to operable status since it had previously failed on June 16, 1983 DMIMS is required to be operable while in Modes 1 and 2 and this report is being submitted in accordance with Action Statement (a) of Technical Specification 3 3.3 10.

The exact cause of the channel failure is unknown at this time.

Maintenance personnel investigating the problem determined that the operation of the Microprocessor portion of the DMIMS was normal and that the failure was in the field equipment which contains accelerometers, cabling, and the pre-amplifier assembly.

PLANS AND SCHEDULE FOR RESTORING TO OPERABLE STATUS The field equipment for the Reactor Vessel Lower Channel of the DMIMS will be repaired and returned to operable status during the next Cold Shutdown.

l