ML20073M057
| ML20073M057 | |
| Person / Time | |
|---|---|
| Site: | LaSalle |
| Issue date: | 05/03/1991 |
| From: | Diederich G COMMONWEALTH EDISON CO. |
| To: | Davis A NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| NUDOCS 9105140237 | |
| Download: ML20073M057 (1) | |
Text
_ _ _ _ - _ _ _ _ _ _ _ _ _. _ _ _ _
ip OC h Commonwealth Edison c
LaSa!!c County Nuclear Station Rural Route e t, Box 220 l
8 V
Marsedles. Ilknois 61341 g g py,g Te!ephone 815/357-6761 g-i t.
pq n m +cyoy r
jar
\\
Quy7 n
%y May 3, 1991 a
f M l.5.
Mr.
A.
Bert Davis Regional Administrator Region III U.S. Nuclear Regulatory Commission 799 Roo:;evelt Road Glen Ellir. Illinois 60137
Dear Sir:
This special report is being submitted in accordance with LaSalle Unit 1 Operating License NPF-11, Technical Specification 4.8.1.1.3 ar.d 6.6.C, regarding a Unit 1, "1B" Diesel Generater test failure.
On April 3, 1991, with LaSalle Unit 1 defueled, the Unit 1 "1B" Diesel Generator (DG) failed to start following a planned 18 month undervoltage auto-start surveillance. This was a valid test failure in accordance with Regulatory Guide 1.108 and Technical Specification 4.8.1.1.3.
The cause of the failure to start was a defective Governor Run Solenoid.
The run solenoid was replaced in accordance with work request LO6520 and the "1B" Diesel Generator was satisfactorily tested by verifying that the Diesel Generator would auto-start and load, followed by the re-performance of the undervoltage auto-start surveillance on April 6, 1991.
At the time of the event, the "1B" Diesel Generator was not required to meet the Limiting Conditions for operation for Unit 1 and the IB Diesel Generator is not required for Unit 2.
/ x* T YO
$f gG. J. Diederich M Station Manager LaSalle Nuclear Station GJD/PSS/mkl cc: Nuclear Licensing Administrator NRC Document Control Desk NRC Resident Inspector IDNS Resident Inspector L
INPO Records Center
)
/O 7105140237 910503 8
PDR ADOCK 05000373
,d;$
s PDR g
< g'
.L * *, s + 4 a g
--