- g ste g 's
/
UNITED STATES
! ?..,
- i NUCLEAR REGULATORY COMMISSION
{
- 3
,;, (;E WASHINGTON, D. C. 20555 y*'dV /
C DUQUESNE LIGHT COMPANY f
OHIO EDISON COMPANY PENNVSYLVANIA POWER COMPANY s
DOCKET NO. 50-334
)
BEAVER VALLEY ~ POWER STATION, UNIT NO.1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 68 License No. DPR-66 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The appl'ication for amendment by Duquesne Light Company, Ohio Edison Company, and Pennsylvania Power Company (the licensees),
dated September 29, 1982, supplemented by letters dated December 8,1982 and February 9,1983, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate,in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission, C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comniission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; i
and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied, I
i t
i 8304200602 830413 PDR ADOCK 05000334 P
PDR I
i
.l
- l,
i
- l 2.
Accordingly, the license is amenced hy changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. OPR-66 is herehy amendec to read as follows:
(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 68, are herehy incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
't 3.
This license amendment is effective as of the date of its issuance.
j FCR THE NUCLEA REGULATORY COMMISSION 1
i I,i
) fg(
- 1 Me
- Targa, et Operating Reactors anch 71 Division of Licensing
Attachment:
Changes to the Technical Specifications i
Date of Issuance:
April 13,1983
-i
~s t
.4
'1
<t G
6 D
1 i
d
ATTAC9 MENT TO LICEf!SE AMENDMEttT AMENDMENT NO. 68 TO FACILITY OPERATING LICENSE NO. DPR-66 l
DOCKET NO. 50-334 Revise Appendix A as follows:
I Remove Pages Insert Pages 3/4 1-19 3/4 1-19 l
3/4 1-20 3/4 1-20 i
j 3/4 1-20a 3/4 1'20a i
3/4 1-20b 3/4 1-20b 3/4 1-20c j
3/4 1-21 3/4 1-21 4
i I
lt
.i l lli:!
l !
I !
i
+
?'
LD1ICC;G CC:OI"'ICN FCR CPEFA!ICN (Centr.usd) b)
The ShMC;.9212; requirerent cf Specificaticn j
3.1.1.1 is dete= ined at least ence per 12 hcurs.
c)
A pcwer distributien : rap is chtained frem the r
'{
nevable incere detecters and FG(3) a.d F H are N
warified to be within their limits within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
d)
A reevaluaticn of each accident analysis of Table 3.1-1 is performed within 5 days; this reevaluation j
shall confirm that the previously analyzed results cf these accidents remain valid for the' duration of cperation under these conditions.
j SGVETANCE REQUIRD22.TS j
c 1
{
t 4.1.3.1.1 Each shutdown and centrol rod nct fully inserted in the core shall be determined to be CPEFABLE by rrcvement of at least 10 steps in any one directicn at least cnce per 31 days.
4.1.3.1.2 Each full length red position shall he deter:rined to be within 12 steps of the asscciated grcup derand counter by verifying the individual red pcsitien at least once per 12 hcurs except during intervals when the Fed Positicn reviation neniter is incperable, then verify the grcup pcsitien at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
f
?
e t
4
.. ~~
l
=See spec:.a1 Test Exceptiens 3.10.2 and 3.10.4 I
i i
i BEAVER VALLEY,- ZIT 1 3/4 1-19 Amendment No, 68 l
e
REACTIVITY CONTRCL SYSTE.'.S POSIh!CN INDICATICN SYSTE'.5-CPERATING LIMITING CONDITION FOR CPERATION
~
o 3.1.3.2 The shutdown and control rod position indication system shall be OPERALLE as follows:
Group Demand CounterII), 1 per group Individual analog rod position instrument channel, 1 per rod + 12 steps (l) accuracy (3) l Automatic Rod Position Deviation Monitor (2), setpoints g 12 steps, or, setpoint verification by recording analog / digital rod position at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
The provisions of Specification 3.0.4 are not applicable to this monitor (3).
(1)
During the first hour following rod motion, the group demand counter is the primary indicator of precise rod position infor-mation, with the analog channels displaying general rod movement information.
For power levels below 50%, a 1-hour thermal soak time is allowed before the analog chann'els are required to.per-form within the specified accuracy.
(2)
For power levels below 50% a one hour thermal soak time is 3
allowed.
Therefore, if a Rod Position Deviation Monitor alarm clears itself within this hour, the alarm is considered invalid.
l (3)
The reporting requirements of Specification 6.9.1.9 are not i
applicable for the group demand counters, analog RPI or Rod Deviation Monitor providing that no actual rod misalignment existed due to the malfunction.
These malfunctions shall be reported in the monthly operating report.
i
-s l
t i
I l
1 i
i l
BEAVER VALLEY - UNIT 1 3/4 1-20 Amendment No. 68 l
I' t
L2'.IT2;G CE: CIT C:; FCR CPEFATIC:: (Centinued)
O APPLICABILITY:
PCCES 1 arx12i
+
ACTION:
If the Rod Positicn Indicating System indicates (2)"a potentially a.
misaligned rod (s), this indication shall be verified inmediately (within 15 minutes) by measuring the analog rod resition channel prinary voltage. If this neasurement confirms that a rod is misaligned, Specificatien 3.1.3.1.3.c is applicable.
i i
b.
With a maxinr.m of cne gcup derand position indicater per hnk incpcrable either:
l.
Verify that all red pcsiticn indicators for the affected bank are CPFE. ELE and that the nest withdrawn rod and the least withdrawn red of the bank are within a raxinum of l
12 steps (indicated ;csi+b.) of each cther at least once per 3 hcurs, or 1
2.
Feduce TEEF. VAL PCHER to less than 50% of PATED THEF. VAL I
within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
c.
With a raxi m cf one analog rod pcsiticn indicator per bank l
i.@le, (follcwing a.cne-hcur thenal soak at less tMn 50% of Rated Themal Pcwer or at anytine when Rated The=al-Pcwer is greater than er ecual to 50%) either, I
jl 1.
Determine r:d pcsiticn for the affected red (s) by neasuring the detector primary voltage, as follcws:
a.
Imnediately l
b.
If the associited 'Ind ncviid ' greater than 6 steps (greater than 12 steps if all the reds in the group have heen detem.ined to he within 6 steps of grcup desand counter indicator hy prirary m itage reasure n ts wit'lin the previcus 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />) c.
At 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> intervals if the affected rod (s) are not fully inserted er withdrawn.
3 i
d.
At 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> intervals if the affected rod (s) are fully j
l inserted or withfrawn, or j
i
[
?
l 1,
s EEAVER VALLEY - UNIT 1 3/4 1-20a Amendment No. 68 i
A CC-'2;G CDI"'ICN FOR CPEPATICN (Centir.ned) -
If the. position of a naxim. of cne red canno-be 9
e.
determined by either the direct reading cf the red position indicators er by reading pri:rary detector voltage masurements, 1.
Determine the position of the non-indicating i
rod indirectly by the novable incore detectors immediately.and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and immediately after any notion of the non-
{
indicating rod which exceeds 24 steps in cra i
direction since the last determiration of the l
2 rod's position.
I 8
f.
If the position of more than one rod cannot be i
determined by either the direct reading of the rod position indicaters er by reading primary detector voltage measurements, then Specification 3.0.3 is applicable.
.4 2.
Reduce 'CM4 REER to less than 50% of PATED "SEP:GL within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
. With the Automatic Rod Deviation Monitor incperable, PCHER d
OPEPATICN may c=ntinue provided that the deviation between the indicated positions is checked by the cperator at least ence per 4 hcurs. The previsiens of Specificatien 3.0.4 i
are not applicable.(3)
+
I I
SCRVEILIANCE REQUIREENTS 4.1.3.2.1 Each of the group demand counters shall be. determined to be OPEPABLE by:
-3
- a. Performing a CFANNEI, GECK by the grcup demand counters within a barA, and cbserving proper overlap
- cf the in-l dicated positions, and
- b. Performing a CFJML CHECK by an interrgsen between the control barA benchboard indicators and the logic solid state indicators in the logic cabinet, and deter-mi dng their agreement within + 2 steps, at least once oer 92 days, i
i During startup ar.d shur.dcwn, cverlap rust be checked for all centrol barks at the respective bark overlap height transitien points.-
EEAVER VALLEY - UNI" 1 3/4 1-2Cb Amendment No. 68 i
f
1 e*
VIILI;s I FICU F.D.E:;TS (Cc-.inued) 4 f
4.1.3.2.2 Each cf the analog red pcsition irdicators shall be de-I te=ined to he CPERAELE by:
i
- a. Performing a CHANNEL CHECK by interccrrparison** between
- i
'i each analog red positicn irdicator and its ccrresperding
,i group demand m M e at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
t
- b. Performing a CHANNEL EUNCTIONAL TEST and CHANNEL CALIBPA-l TION at least once per 18 nonths.
i I.
4.1.3.2.3 The Autcznatic Rod Deviation Monitor shall be determined to be CPERABLE by performing a functional test at least cnce per 7 days, j.
ard the deviation between the pcsitien indicated by the individual analog red pcsitien instru ent channel and the pcsiticn irdicated by the ccrresponding grcup derard counter shall be checked ** ranually for
.. j each red at least cre.e per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
i I
i i
i i
.}
GFor Ccre PHYSICS TESTING in Mcde 2, prirary detector mitage measure-1 l
mnts ray he used to deterrine the ;csitien cf rods in shutdcwn barAs A
.i and B and centrol barAs A and B for the purpcse of satisfying Specifica-tien 3.1.3.2.
During Mcde 2 cperaticn, red pcsitien irdicaters for shut-o down barAs A and B and centrol barAs A and 3 ray deviate Sm the grcup derand indicators by greater than,+ 12 steps during reactor startup and shutdcwn cperaticns, while reds are being withdrawn or inserted.
If
[
the rod positicn indicators for shutdcwn harAs A and B and centrol banks r
A and B deviate by greater than + 12 steps from the grcup derard indicator,
-l red withdrawal cr insertien tray continue until the desired group height is j
achieved. When the desired grcup height is achieved, a one hour scak time is a.cwed telow 50% reactor gewer to permit stabiliration cf the
[;
red pcsit_.cn analog indicators. To attain therral ec,uilibrium during l
the cne hcur scak tire, the absolute value cf red action shall not exceed
}
6 steps.
{
I i
-s
,ll
- Fcr pcwer levels belcw 50% cne hcur therral "scak tire" is permitted.
During this scak ti:re, the absolute value cf red reticn is limited to six sters.
4 l
i l1
!i l}
i
~
i l1 l
EEAVER VALLEY "- UNIT 1 3/4 1-20c Amendment No. 68 l'
t I
,j l,
Ii f3
. ~..
.\\
6
REAC"'IVI"Y C:GCL SYSTD'S t
PCSITICN DIICATICN SYSTD!-SHUMN LIMITING CIDITICN FOR CPERATICN me group derrand :csitien indicaters shall be OPEFABLE and 3.1.3.3 I
capable cf detectining within + 2 steps the derrand pcsition for each 1,
shutdown or control rod not fully inserted.
APPLICABILITY:
20 mS 3*,
4*, and 5*
t ACTICN:
i 5;ith less than the abcVe required group de: rand pcsition indicatcrs l
OPEFABLE, cpen the reactor trip system breakers.
j I
i SURVEILIANCE RECUIRDINTS
{
4.1.3.3 Each of the above. @ ed group derrard position indicatcr(s) shhll be determined to be CPERAELE by move: rent,cf the associated cchtrol l
rcd at least 10 steps in any cne direction at least once per 31 days when the reacter ecclant system pressure is > 400 psig.
Ie
-x i
- Nith the reacter trip system breakers in the clcsed pcsition.
-EEAVER T M - UNIT 1 3/4 1-21 Amendment No. 68
..