.v LOUISIANA f we ouAnoNoe Smm POWE R & LlG H T/ P O BOX 6008. NEW CALEANS. LOUISlANA 70174. (504) 366 2345
$uSN2vsE L V. MAURIN April 8, 1983 W3183-0110 Q-3-A35.07 Mr. John T. Collins, Regional Administrator, Region IV U. S. Nuclear Regulatory Commission 7
611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76012
SUBJECT:
Waterford SES Unic No. 3 APRI5G33 o
Docket No. 50-382 d
Potentially Reportable Deficiency No. 105 U
" Corrosion on General Electric H-L Time Overcurrent Relays in 480V Switchgear" Final Report
REFERENCE:
Telecon from M. A. Livesay to J. Boardman on March 11, 1983
Dear Mr. Collins:
On March 11, 1983 a problem with corrosion on GE H-L Time Overcurrent Relays in 480V Switchgear was reported to your office as Potentially Reportable Deficiency No. 105. This letter is to inform you that after further evaluation, this condition is not considered to be reportable pursuant to the requirements of 10CFR50.55(e) for the following reasons:
- 1) Before these relays go into service they are fully inspected, tested, and calibrated. Any misoperation during this phase would immediately be investigated for its cause.
- 2) These relavs are used for additional overcurrent protection on MCC feeders and do not perform any primary safety function. They are being used to essentially duplicate protection performed by the ECS programmers for the switchgear breakers. The design and operation of this electrical system would not be compromised if these relays failed to operate.
47 Very truly yours, f
f v maw L. V. Maurin LVM/ MAL:keh G3041902iO 2
I
~%Y John T. Collins W3I83-0110 Page 2 cc: