. _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _

4 GPU Nuclear Corporation 0 0 Nuclear m:3sr*

Middletown, Pennsylvania 17057-0480 (717)944 7621 Writer's Direct Dial Number:

(717) 948-8005 September 9, 1994 C311-94-2116 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555

Dear Sir:

Subject:

Three Mile Island Nuclear Station, Unit 1 (THI-1)

Operating License No. DPR-50 Docket No. 50-289 Revised Emergency Response Data System (ERDS)

Data Point Library Sheets Pursuant to 10 CFR 50 Appendix E, Part VI, Section 3.a, attached are revised data point library sheets for the THI-1 Emergency Response Data System (ERDS).

These changes became effective on August 4, 1994, and do not affect the transmission format or computer communication protocol. The following is a summary of the attached changes:

Point ID

' Changes i

A0992 New point measures wind velocity at site between 0 and 100 mph.

A0993 New point measures wind direction at site.

A0995 New point measures temperature delta t between 150 ft. and 33 ft.

A1000 New point measures radioactivity in plant water discharge after dilution.

Sincerely,

[d W

T. G. Brou ton DVH/mkk 1I"IEO 9409190225 940909 Attachment PDR ADOCK 05000289 P

pnn cc:

M. G. Evans - TMI Senior Resident Inspector h

R. W. Hernan - TMI-1 Senior Project Manager J. R. Jolicoeur - Senior Emergency Preparedness Specialist t g T.T.gg,igc,,,,gog,jto}7igo,r I

ubs$'aEyYr" General Pubhc Utskties Corporation s a

I DATA POINT LIBRARY REFERENCE FILE l

DATE:

8/4/94 REACTOR UNIT:

TM1 DATA FEEDER:

N/A l

NRC ERDS PARAMETER:

WIND SPEED POINT ID:

A0992 l

PLANT SPEC POINT DESC.:

WW-WS-100A WIND SPEED GENERIC /COND DESC.:

Wind Speed at Reactor Site ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

MPH l

ENGR UNITS CONVERSION:

Linear MINIMUM INSTR RANGE:

0.0 l

MAXIMUM INSTR RANGE:

100.0 l

l l

ZERO POINT

REFERENCE:

N/A l

REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A l

SENSOR LOCATIONS:

Meteorological tower at north end of island (TMI) at 100 ft elevation.

ALARM / TRIP SET POINTS:

N/A UNIQUE SYSTEM DESC.:

Measures wind velocity at site between 0 and 100 MPH.

l

I DATA POINT LIBRARY REFERENCE FILE l

DATE:

8/4/94 REACTOR UNIT:

TM1 t

DATA FEEDER:

N/A l

NRC ERDS PARAMETER:

WIND DIR POINT ID:

A0993 PLANT SPEC POINT DESC.:

WW-WD-100A WIND DIRECTION GENERIC /COND DESC.:

\\Nind Direction at Reactor Site ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

DEGREES ENGR UNITS CONVERSION:

Linear

[

MINIMUM INSTR RANGE:

0.0 l

f MAXIMUM INSTR RANGE:

540.0 ZERO POINT

REFERENCE:

N/A l

REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A j

i SENSOR LOCATIONS:

Meteorological tower at north end of island (TMI) at 100 ft. elevation.

ALARMfrRIP SET POINTS:

N/A-UNIQUE SYSTEM DESC.:

Measures wind direction at site.

l

i l..-

e.

I i-DATA POINT LIBRARY REFERENCE FILE.

i DATE:

8/4/94 i

REACTOR UNIT:

T M 1-

]

DATA FEEDER:

N/A NRC ERDS PARAMETER:

STAB CLASS POINT ID:

A0995 l

PLANT SPEC POINT DESC.:

WW-TR-150A/33A DELTA T-GENERIC /COND DESC.:

Air Stability at the Reactor Site -

ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

DEGF ENGR UNITS CONVERSION:-

Linear j

MINIMUM INSTR RANGE:

-8.0 MAXIMUM INSTR RANGE:

20.0 I

ZERO POINT

REFERENCE:

N/A' REFERENCE POINT NOTES:

.N/A 1

PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

N/A SENSOR LOCATIONS:

Meteorological tower at north end of island (TMI) at 150 ft. & 33 ft. elevation ALARM /TPIP SET POINTS:

N/A UNIQUE SYSTEM DESC.:

Measures ternperature delta _ between 150 ft.' and 33 ft. (AT = T,so - T )

.I 33

a 0

  • DATA POINT LIBRARY REFERENCE FILE DATE:

8/4/94 REACTOR UNIT:

TM1 DATA FEEDER:

N/A NRC ERDS PARAMETER:

EFF LIO RAD POINT ID:

A1000 PLANT SPEC POINT DESC.:

RM-L7 PLANT WATER DlS RAD MON GENERIC /COND DESC.:

Radioactivity of Released Liquids ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

CPM 1

ENGR UNITS CONVERSION:

Exponential MINIMUM INSTR RANGE:

10.0 MAXIMUM INSTR RANGE:

1000000.0 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATIONS:

Water discharge to river at west side of island.

ALARM / TRIP SET POINTS:

N/A UNIQUE SYSTEM DESC.:

Measures radioactivity in plant water discharge after dilution.