Interim Deficiency Rept Re Potentially Unsafe Situation Concerning Tripping of Reactor Coolant Pumps During Certain Primary Sys High Void Fraction Conditions.Pump Trip Criteria Will Be Established Per NRC Generic Ltr 83-10
ML20072N908
Person / Time
Site: Midland
Issue date: 07/11/1983
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, 22265, 79-03-#8, 79-3-#8, GL-83-10, NUDOCS 8307180171
Download: ML20072N908 (2)


Text

-

CORSumEIS POWar aa,n., w cm Q

Q Vice President - Projects, Engineering and Construction General offices: 1945 West Parnell Road, Jackson, MI 49201 e (517) 783 0453 July 11, 1983 79-03 #8 Mr J G Keppler, Regional Administratior US Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND ENERGY CENTER PROJECT DOCKET NOS 50-329 AND 50-330 SMALL BREAK / REACTOR COOLANT PUMP OPERATION INTERACTION FILE 0.4.9.28 SERIAL 22265

References:

CPCo letters to J G Keopter; Same

Subject:

1) Serial Howe-221-79, dated Au6ust 1% 1979
2) Serial Howc-271-79, dated October 19, 1979
3) Serial Howe-25-80, dated February 8, 1980 4)

Serial 9770, dated October 10, 1980

5) Serial 12010, dated Itar 29, 1931
6) Scrini 14268, dated December 4, 1981 7)

Serial 17540, dated July 9, 1982 This letter, as were the referenced letters, is an interim 50.55(e) report concerning a potentially unsafe situation with respect to the tripping cf reactor coolant pumps during certain primary system high void fraction conditions.

On February 8, 1983 the NRC staff issued a generic letter (83-10) to all licensees requesting final action to establish reactor coolant pump trip criteria. This letter included a list of questions and considerations which the NRC staff requires more information on as backup documentation to support the selected RC pump trip criteria.

The B&W Owners Group is in the final stages of developing an analysis program which will establish the RC pump trip criteria and provide the requested backup analysis. A description of this program will be sabmitted by.

Consumers Power Company to the NRC staff within two weeks in response to the generic letter.

8307180171 830711 OC0783-0012A-MP01 PDR ADOCK 05000329 TM]

S PDR Il6

5

\\,.

2 The schedule for this program indicates preliminary information will be

. supplied by October, 1983 and a final report will be supplied by the end of

1983.

Another report, either interim or final, will be submitted on or before February 1,1984.

JWC/cd CC.CBechhoefer, ASLB Panel

'LBernabei, CAP RSDecker, ASLB Panel FPCowan, ASLB Panel JHarbour, ASLB Panel AS&L Appeal Panel MMCherry, Esq MSinclair BStamiris CRStephens, USNRC WDPaton, Esq. USNRC FJKelley, Attorney General' SHFreeman, Esq. Asst Att Gen WHMarshall GJMerritt, TNK&J INPO Records Center Document Control Desk, NRC Reg III RJCook, NRC Inspector-Midland Site