Informs of Plans to Modify Once Through Steam Generator Tube Rupture Guidelines & Emergency Procedures,Per 830629 Telcon.Mods Will Be Completed by 830801.Limits Correspond to Site Emergency Declaration Limits
ML20072N449
Person / Time
Site: Crane 
Issue date: 07/08/1983
From: Hukill H
GENERAL PUBLIC UTILITIES CORP.
To: Stolz J
Office of Nuclear Reactor Regulation
References
5211-83-196, NUDOCS 8307150323
Download: ML20072N449 (1)


Text

GPU Nuclear g

g{

P.O. Box 480 Middletown, Pennsylvania 17057 717-944-7621 Writer's Direct Dial Number:

July 8, 1983 5211-83-196 Office of Nuclear Reactor Regulation Attn: John F. Stolz, Chief Operating Reactors Branch No. 4 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C.

20555

Dear Sir:

Three Mile Island Nuclear Station, Unit 1 (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 OTSG Tube Rupture Guidelines Per our phone conversation of June 29, 1983 with members of your staff, this letter is being sent to formally inform you of our plans to modify the tube rupture guidelines and emergency procedures you have been reviewing.

Current procedures require isolation of the affected steam generator (s) when off-site dose rates or dose projections exceed 50 mr./hr. whole body.

The planned change will modify this requirement to 50 mr./hr. whole body or 250 mr./hr. thyroid. Both of these limits correspond to the Site Emergency declaration limits. The guidelines and procedures will be revised to reflect this change by August 1, 1983.

Sincerely, D.

k:

Director, TMI-1 HDH:MJG:j rg cc:

H. Silver QO 8

8 0

8307150323 830708 PDR ADOCK 05000289 P

PDR GPU Nuclear is a part of the General Public Utilities System