PHILADELPHIA ELECTRIC COMPANY 23O1 MARKET STREET P.O. BOX 8699 1881 -1981 PHILADELPHI A, PA.19101 1215)841-4502 tf1C E -PR ESI D E N T CN4.thEE R6MG AND RESE ARCN June 20, 1983 Mr. A. Schwencer, Chief Licensing Branch No. 2 Division of Licensing U.S. Nuclear Regulatory Commission Washington, DC 20555 Subj ect:

Limerick Generating Station, Units 1 & 2 NUREC-0737, Item II.K.3.18, " Modification of Automatic Depressurization System Logic"

Reference:

A. Schwencer to E. G. Bauer, Jr., letter dated May 23, 1983 File:

GOVT l-1 (NRC)

Dear Mr. Schwencer:

This letter provides our proposed resolution to TMI Item II.K.3.18 in accordance with your May 23 request. We will implement option 4, as outlined in the BWR Owners' Group Generic Response to NUREG-0737 Item II.K.3.18.

Specifically, modifications will be made to add a timer which would bypass the high drywell pressure permissive af ter a sustained low water level and to add an ADS manual inhibit switch.

Prior to implementation of the modification we will provide the necessary justification for the bypass timer setting and our plans for periodic testing of the timer and the inhibit switch.

In addition, operation of the inhibit switch will be addressed in the Plant Emergency Procedures.

0 8306230276j3 2

PDR DOCK PDR l

1 0

- We have considered the feasibility of implementing this modification prior to fuel load in August,1984 and are unable to commit to this date. We believe that such a commitment with its required plant unique analysis and subsequent equipment purchases may impact our fuel load schedule.

Therefore, ' this modification will be implemented on Unit 1 by the completion of the first refueling outage af ter fuel load, based on equipment availability. The same modification will be made on Unit 2 prior to fuel load.

Sincerely,

,$SWf

(

Copy to: See Attached Service List

~,

e oc: Judge Lawrence Brenner Judge Richard F. Cole Judge Peter A. Morris Troy B. Conner, Jr., Esq.

Ann P. Hodgdon Mr.' Frank R. Ibnano Mr. Robert L. Anthony Mr. Marvin I. Iewis Judith A. Dorsey, Esq.

Charles W. Elliott, Esq.

Jacqueline I. Ruttenberg

'Ihanas Y. Au, Esq.

Mr. 'Ihanas Gerusky Director, Pennsylvania Bnergency Managenent Agency Mr. Steven P. Hershey James M. Neill, Esq.

Donald S. Bronstein, Esq.

Mr. Joseph H. hhite, III David Wersan, Esq.

Robert J. Sugannan, Esq.

Martha W. Bush, Esq.

Atanic Safety and Licensing Appeal Board Atcmic Safety and Licensing Board Panel Docket and Service Section l

l I

9

..