Responds to IE Bulletin 83-03, Check Valve Failures in Raw Water Cooling Sys of Diesel Generators. Affected Check Valves Associated W/Each Diesel Generator Listed
ML20072C706
Person / Time
Site: Salem  
Issue date: 06/07/1983
From: Liden E
Public Service Enterprise Group
To: Allan J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
REF-SSINS-6820 IEB-83-03, IEB-83-3, NUDOCS 8306210176
Download: ML20072C706 (3)


Text

(

O PSEG Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department June 7, 1983 Mr. James M. Allan, Acting Administrator Region 1 U.S.

Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Allan:

IE BULLETIN 83-03 CHECK VALVE FAILURES IN RAW WATER COOLING SYSTEMS OF DIESEL GENERATORS SALEM GENERATING STATION UNIT NOS.-l AND 2 In response to the subject Bulletin, PSE&G has reviewed its pump and valve test program and has identified the following check valves associated with each diesel generator as being affected.

Salem Unit 1 Salem Unit 2 11 & 12 SW34 21 & 22 SW34 11 & 12 SW36 21 & 22 SW36 11 & 12 SW38 21 & 22 SW38 11,12 & 13 SW44 21,22 & 23 SW44 11 & 12 SW47 21 & 22 SW47 These check valves are covered by Salem's pump and valve testing program and their operation is verified every ninety (90) days.

There have been no problems with these valves.

In accordance with Item 2 of the Bulletin, we have considered various test methods to verify the integrity of the valve internals, and we have elected to conduct radiographic examina-tions of the internals with the valves in place.

These examina-tions will be conducted during each refueling outage.

The Unit 2 valves identified above were examined radiographi-cally during the current outage, and the integrity of the internals of each valve was satisfactory.

Initial radiographic examinations on Unit 1 valves will be conducted during the next refueling outage, currently scheduled to begin in August 1984.

The results of this inspection will be submitted to the NRC within 90 days of completion of the test.

8306210176 830607 PDR ADOCK 05000272

/N O

PM g6 The Energy People 71 0

95-2168 i80V; t 182

w 1

l Mr. James M.

Allan U.S. Nuclear Regulatory Commission 6/7/83 y,

b.

Should you have any questions, please-:do not hesitate to contact us.

Very truly yours,

~

1

. A. Liden-Manager - Nuclear Licensing and Regulation CC:

U.

S.

Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 Mr. Donald C.

Fischer Licensing Project Manager Mr. Leif Norrholm Senior Resident Incpector 4

2

.... -, -, =.

,,m--7._,-...

m -- r r, #,

--,yy. - -, -.,, _ _ _ -.,, - -,

,,-,.3-..

,---v.-4,,-.-

. ~

y -- _

.. c-STATE OF NEW JERSEY

)

)

SS..

COUNTY OF SALEM

)

RICHARD A. UDERITZ, being duly sworn.according to law deposes and says:

I am a Vice President of Public Service Electric and Gas Company, and as such, I find the matters set forth in our letter dated June 7, 1983, in response to IE Bulletin 83-03 concerning Check Valve Failures in Raw Water Cooling Systems of Diesel Generators, are true to the best of my knowledge, information and belief, bd

~

RICHARD A. ~U DERITV l

Subscribed and sworn to before me this 8 "

day of Tune 1983 St

~

/ ~ JotayY Publ"Ic of N94 Jersey Run<h rH L von f".iCHf 51 JR.

( n:.-v y D.tf;:, rtru n isnj s

r My Commission expires on My c -

,:. rec l

l L

t