ML20072C086

From kanterella
Jump to navigation Jump to search
Final Potentially Reportable Deficiency Rept 99 Re Magnetrol Model Ldn Level Switch Design.Level Switches Not Class IE Devices & Not Required for Safe Shutdown.Condition Not Reportable Per 10CFR50.55e
ML20072C086
Person / Time
Site: Waterford 
Issue date: 02/28/1983
From: Maurin L
LOUISIANA POWER & LIGHT CO.
To: Jay Collins
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, W3I83-0064, W3I83-64, NUDOCS 8303080298
Download: ML20072C086 (1)


Text

LOUISIANA 24a ouAnoNoe S1nur POWER & LIGHT P O BOX 6000

  • NEW OnLEANS. LOUISlANA 70174 (504) 366-2345

+

MIDDLE SOUTH utiuTIES SYSTEM February 28, 1983 L. V. MAURIN Vn.e Pressdent Nuclear Operations W3183-0064 7 3 A35.ve i

~(

Mr. John T. Collins, Regional Administratt

?

h

@bl 8.N Region IV I

I U. S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76012

't

SUBJECT:

Waterford SES Unit No. 3 Docket No. 50-382 Potentially Reportable Deficiency No. 99 "M gnetrol Model LDN Level Switches-Design Deficiency" Final Report

REFERENCE:

Telecon from M. A. Livesay to W. A. Crossman on January 28, 1983

Dear Mr. Collins:

On January 28, 1983 a problem with Magnetrol International, Inc. liquid level switches was reported as Potentially Reportable Deficiency No. 99.

Leakage through the nameplate rivet holes had been discovered on these type submersible style switches. This leakage could cause an electrical short and corrosion to the switch mechanism which could prevent the switch from operating.

After further investigation, it was determined that although the level switches have an I6C class code of N2S1, they are not class IE devices and are not required for safe shutdown of the plant. As a result, this condition has been determined to be not reportable.

1

/

$ $$fs'4 L. V. Maurin LVM/ MAL:keh cc:

1) Director 3)

E. L. Blake Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.

20555 (with 15 copies of report) f

2) Director 4)

W. M. Stevenson Office of Management h(

Information and Program Control U. S. Nuclear Regulatory Commission Washington, D. C.

20555 (with I copy of report) 8303080298 830228 PDR ADOCK 05000382 S