ML20071M368

From kanterella
Jump to navigation Jump to search
Forwards NPDES Noncompliances for Permit 120048151.On 820821,total Suspended Solids Limit for Plant Discharge Exceeded Limit.Caused by Loss of Hydrogen Peroxide Injection from Temporary Sys.Permanent Sys to Be Installed
ML20071M368
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 09/10/1982
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8209270101
Download: ML20071M368 (3)


Text

_

x Commonw cith Edison

.) Hural Route #1, Box 220LaSalle County Nuclear Station o

v Marseilles, II!inois 61341

' V _ )q

\\

Telephone 815/357-6761 September 10, 1982 James G. Keppler Region,il Administrator Direc tor of Regulatory Operations - Region 111 i

U. S. Nuclear Regulatory Cammission 799 Roosevelt Raad Glen Ellyn, Illinois 60137

Dear Sir:

In accordance with LaSalle County Station Unit 1 Facility Operating License NPF-ll, Appendix B, Section 3.2, we are submittirg to you a copy of the NPDES noncompliances for LaSalle County Nuclear Generating Station Permit No. 1 LOO 48151.

G. J. Diederich Superinter. dent LaSalle County Station l

l t

l ML I

CJD/FRL/JG"/jfe l

(

Cnclosure cc.

D'/R Report 1

f20907o101920910 R 6 DOCK 05000373 S

PDR SEP 2 21982

- Yb b

3

~

h Commonwoelth Edloon LEStila County Nucitar Station

1) RuralRouta #1. Box 220 c

- Marseilles, lilinois 61341 U

Telephone 815/357 6761 September 10, 1982 U. S. Environmental Protection Agency Region V, Enforcement Division ATTN: Chief, Compliance Unit 230 South Dearborn Street Chicago, Illinois 60604 Illinois Environmental Protection Agency Division of Wster Pollution Control Compliance Management Unit 2200 Churchill Road Springfield, Illinois

SUBJECT:

NPDES Noncompliances For LaSalle County Nuclear Generating Station - Permit No. ILOO48151

Dear' Sir:

In accordance with Standard Condition 12, we wish to submit the following notice of noncompliances, which are listed chronologically in the attached table.

If there are any questions, please contact Joe Williams of my staf f at (815)-

357-6761, extension 201.

J. KEL G

J. Diederich Superintendent LaSalle County Station cJD/

/JGW/j f e cc: Director of Water Quality, Environmental Affairs Manager, Nuclear Stations Division

LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:

ILOO48151

~

NONCOMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTION:

001c Low Volume Waste Regen. Wastes Soln.

Discharge Tank PARAMETER AND PERMIT LIMIT:

Total suspended solids,15 mg/l NONCOMPLIANCE, DATE, AND DURATION:

23 mg/1, August 21, 1982, 2-1/2 hrs.

CAUSE OF NONCOMPLIANCE:

i Excessive amounts of soluble iron collected on the Make-up Demineralizers due to loss of Hydrogen Peroxide Injection from the temporary system. This iron was discharged to this outfall as insoluble iron during regeneration of the Demineralizer.

CORRECTIVE ACTION:

A permanent Hydrogen Peroxide Injection System is to be installed as soon as equipment can be purchased and delivered.

Expected completion date is January 1, 1983.

In addition a once a shift check of the Hydrogen Peroxide system is being added to the operators rounds.

i DATE RECOGNIZED AS A VIOLATION _:

August 23, 1982 DATE INVESTIGATED:

August 25, 1982 t

._