r DESIGNATED ORIGINAL W[

e Certified By BALTIMO'RE GAS AND ELECTRIC COMPANY P.O. SOX 1475 mALYtMONE. M AnvLAND 2f 2o3 MUCLEAe #0tfEN DSPARTMENT CAbvC27 CLsH5 WUCLEAR POWFA PLAser W6;f, asAkvkAseO 20E3r Juiy 19,1982 Docket No. 50-317 Mr. Ronald C. Maynes, Director License No. DPR-53 Office of Inspectim and Gnforcement U. S. Nuclear Regulatory Commisssion Region 1 631 Park Avenue King of Pen =<ia, PA.19406 SUB3ECT:

LER 32 35, Unit i Dear Mr. Maynes This letter is to confirm our verbal notification of your Mr. Ralph Architzel of the discovery that the level in one afety injection tank was found to be below minimum Technical Specification Limits.

At 001S on 7 17 82 with Unit 1 in Mode I, it was discovered that 115 safety injection tank level indicated 192 inches on the narrow rance indicator, but only 180 inches on the wide range indicator. The Technical Specification Limit is 117 inches. While the operator was investigating the discrepancy, the narrow range indicator decreased below the minimum scale reading of 184 inches. This is a vloration of Technical Specification 3.5.1.b. Water was added te the tank and minimum level achimed at 0108, terminating the event.

A complete description of the events leading to this discovery and further corrective actions will be addressed in the follow-up report.

Very truly yours, b

L. 5. Russell Plant Superintendent LBRrfld R. M. nour, lass cer

7. A.Tiernan R. E. Architzei Director, Office of Management L. B. Russell information & Program Control G. $. Pavis 8208020387 820719 g1ll PDR ADOCK 05000317 S