ML20070S247

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Accident Temp Effects on Containment Level Measurement.Investigation Has Limited Need for Corrective Action to Steam Generator Level Transmitters. Bechtel Investigating String Error.Next Rept by 830506
ML20070S247
Person / Time
Site: Midland
Issue date: 02/01/1983
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, 20689, 82-05, 82-5, NUDOCS 8302040328
Download: ML20070S247 (2)


Text

-

1 CORSum8fS v

Power James W Cook Vice President - Projects, Engineering and Construction General offices: 1945 West Pernell Road, Jackson, MI 49201 + (517) 788-0453 February 1, 1983 82-05 #3 Mr J G Keppler, Regional Administrator US Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND ENERGY CENTER PROJECT -

DOCKET NOS 50-329 AND 50-330 ACCIDENT TEMPERATURE EFFEC'IS ON CONTAINMENT LEVEL MEASUREMENT FILE:

0.4.9.61 SERIAL:

20689

Reference:

J W Cook letters to J G Keppler, same subject:

1) Serial 16192, dated May 14, 1982 2)

Serial 19053, dated September 28, 1982 This letter, as were the referenced letters, is an interim 50.55(e) report on accident temperature effects on containment level measurement.

Investigation has limited the need for corrective action to steam Fenerator level transmitters.

It has been determined that instrument string rtror for this equipment under accident conditions exceeds that allowed to establish the steam generator ECCS control setpoints. Bechtel has been directd to investigate and recommend methods of reducing string error.

Another letter, either interim or final, will be provided on or before May 6, 1983.

l JWC/WRB/AllB/cd CC:

RJCook, NRC Resident Inspector Midland Nuc1 car Plant Document Control Desk, NRC Washington, DC 8302040328 830201 PDR ADOCK 05000329 0

PDR B

2 1993 OC0183-0058A-MP01 Tff

2 a

I Serial 20689 82-05 #3 CC:

CBechhoefer, ASLB Panel RSDecker, ASLB Panel FPCowan, ASLB Panel AS&L Appeal Panel MMCherry, Esq MSinclair BStamiris CRStephens, USNRC WDPaton, Esq, USNRC FJKelley, Esq, Attorney General SHFreeman, Esq, Asst Attorney General WHMarshall GJMerritt, Esq, TNK&J l

OC0183-0058A-au01