Application for Amend to License NPF-29,revising TS 3.8.1.1.b.2 & 3.8.1.2.b.2 to Require Min Vol of 57,200 Gallons in Fuel Oil Storage Tanks
ML20070D305
Person / Time
Site: Grand Gulf 
Issue date: 02/22/1991
From: Cottle W
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20070D308 List:
References
GNRO-91-00017, GNRO-91-17, NUDOCS 9102280198
Download: ML20070D305 (4)


Text

.-

i

-or= Ent rgy F"'~ a oa~a" "* '"*-

Operations L

W. L Cottle February 22, 1991 U.S. Nuclear Regulatory Commission Mall Station P1-137 Washington, D.C.

20555 Attention:

Document Control Desk SUIUECT:

Grand Gulf Nuclear Station Unit 1 Docket No. 50-416 License No. NPF-29 Revised Minimum Storage Volumes For Fuel Oil Storage Tanks Proposed Amendment to the Operating License (PCOL-90/13)

GNRO-91/00017 Gentlemen During preparations for an Electrical Distribution System Functional Inspc %1on (EDSFI) at the Grand Gulf Nuclear Station (GGNS), Entergy Operations, Inc. determined that the minimum usable fuel oli volume for the Division I diesel generator storage tank was 61,914 ge11ons.

Contrary to this, Technical Specifications (TS) 3.8.1.1.b..'

and 3.8.1.2.b.2 require a minimum volume of 57,200 gallons.

Similarly, a new calculation of the Division III fuel oil requirements identifled a minimum usabic volume of 41,158 gallons which is greater than the Technical Specification value of 39,000 gallons.

The new calculation for the Division II fuel oli requirements verified that the current TS value of 57,200 gallons bounds the newly calculated value of 53,530 gallons.

The revised calculations for the Divisions 1, 11 and 111 storage tanks were reviewed by the EDSF1 team during November - December, 1990.

Accordingly, a proposed change to the Operating License har been l

developed to revise these values.

The TS value for Division 11 is also revised to maintain the existing consistency between the Division 1 and l

11 volume values.

It should be noted that while the above newly calculated volumes exceed the TS required minimum usable volumes, the minimum fuel oil storage t ank volumes were maintained above the newly calculated values because of conservative input values pertaining t o the amcur.t of unusable fuel oil volume in the original calculat.icns.

Therefore, GGNS always met the recalculated fuel oil volumes for the three diesel generat ors by performance of the current surveillance procedures.

I 9102280198 910222 i

PDR ADOCK 05000416 0()\\

l P

PDR

\\

A9012141/SNLICFLR - 1 i

Q Q f' #

\\

_ _. _ _ _. _ __ _ _ ___ _. _. - m _ _._

i February 22, 1991 GNRO-91/00017 Page 2 of 4 l

Grand Gulf has implemented a Technical Specification Position Statement (i.e., TSPS 133) which provides administrative control of the fuel oil storage tank minimum. volume values until the proposed Operating Liccuse amendment is approved. This position statement will ensure that an adequate fuel oil inventory is maintained in the storage tanks.

In accordance with the provisions of 10CFR50.4 the signed original of the requested amendment is enclosed. Attachment 2 provides the technical justification and discussion to support the requested amendment.

This amendment has been reviewed and accepted by the Plant Staff keview Committee and the Safety Review Committee.

Based on the guidelines presented in 10CFR50.92 Entergy Operations has concluded that hiw prnposed arnendment involves no significant hazards considerations.

Yours truly, w y~

Cem WTC/PRStams attachment's 1.

Affirmation per 10CFR50.30 2.

GGNS PCJL-90/13 cci (See Next Page)

I i

A9012141/SNLICFLR - 2

February. 22, 1991 GNRO-91/00017-Page 3 of 4 cci Mr. D. C. Hintz (w/a)

Mr. J. Mathis (w/a)

Mr. R. B. McGehee (w/a)

Mr. N. S. Reynolds (w/a)

Mr. H. L. Thomas (w/o)

Mr. Stewart D. Ebneter (w/a)

Regional Administrator U.S. Nuclear Regulatory Commission Region 11 101 Marietta St.,

N.W., Suite 2900 Atlanta, Georgia LO323 Mr. L. L. Kintner, Project Manager (w/a)

Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Hall Stop 11D21 Washington, D.C.

20555 Dr. Alton B. Cobb (w/a)

State Health officer

~ State Board of Health P. O. Box 1700-Jackson, Mississippl 3920$

l l

e h

i I

t A9012141/SNLICFLR - 3 I

I

_ _ _. _ ~ _ - - - -

4 BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION LICENSE NO. NPF-29 DOCKET NO. 50-416 1

IN THE MATTER OF

)

MISSISSIPPI POWER fr LIGHT COMPANY and SYSTEM ENERGY RESOURCE;, INC.

and SOUTH MISSISSIPPI ELECTRIC POWER ASSOCIATION and ENTERGY OPERATIONS, INC.

AFFIRMATION I, W. T. Cottle, being duly sworn, state that I am Vice President, Operations GGNS of Entergy Operations, Inc.: that on behalf of Entergy Operations, Inc., System Energy Resources, Inc., and South Mississippi Electric Power Association I am authorized by Entergy operations, Inc. to sign and file with the Nuclear Regulatory Conunission, this application for amendment of the Operating License of the Grand Gulf Nuclear Stations that I signed this application as Vice President, Operations GGNS of Entergy operations, Inc.: and that the statements made and the matters set forth therein are true and correct to the best of my knowledge, information and

belief, c o. N+t:a: -

W. T. Cottle STATE OF MISSISSIPPI COUNTY OF CLAIBORNE SUBSCRIBED AND SWORN To before me, a Notary Public, in and for the County and State above named, this __3_t day of hbum 1991.

r J

( S E *.L) c5.

AesaboQm My conunissien explces s a -- w-un A9012141/SNLICFLR - 5