ML20070A827

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in IE Insp Repts 50-327/82-20 & 50-328/82-20.Corrective Actions:Boric Acid Storage Tank Ventilation Sys Temporarily Modified to Prevent Release of Radioactive Matls to Auxiliary Bldg
ML20070A827
Person / Time
Site: Sequoyah  
Issue date: 11/08/1982
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20070A794 List:
References
NUDOCS 8212090365
Download: ML20070A827 (2)


Text

.

s=

RC pECTIENNESSEE VALLEY AUTHORITY

,j,l} Irk -

CH ATTANOOGA, TENNESSEE 374ol Chestnut Street Tower II

^7 November 8, 1982 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

SEQUOYAH NUCLEAR PLANT UNITS 1 AND 2 - NRC-0IE REGION II INSPECTION REPORf 50-327/82-20 AND 50-328/82 RESPONSE TO VIOLATION The subject OIE inspection report dated October 7,1982 from D. M. Verrelli to H. G. Parria cited TVA with one Severity Level V Violation. Enclosed is our response to the subject inspection report.

If you have any questions, please get in touch with R. H. Shell at FIS 858-2688.

To the best of my knowledge, I declare the statements contained herein are complete and true.

Very truly yours, TENNESSEE VALLEY AUTHORITY M

L. M. Mills, hnager Nuclear Licensing Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 l

l 8212090365 821130 PDR ADOCK 05000327 G

PDR An Equal Opportunity Employer l.

2

9

~

e ENCLOSURE RESPONSE - NRC INSPECTION REPORT NOS. 50-327/82-20 AND 30-328/82-20 D. M. VERRELLI'S LETTER TO U. G. PARRIS DATED OCTOBER 7, 1982 50-327, 50-328/82-20-01 10 CFR 20.203(d) and t E TVA Health Physics Manual as implemented by paragraph III.B.6 of Radiological Centrol Instruction, RCI-1, requires that each airborne radioactivity area as defined in 10 CFR 20.203(d) be conspicuously posted with a sign or signs.

Contrary to the above, airborne radioactivity areas of the Auxiliary Building were not posted as required in that maximum permissible concen-trations (MPC) of Xe-133 were exceeded on April 28, 1982, by the following amounts without posting: Elevation 669-4.52 MPC, Elevation 690-5.61 MPC, Elevation 714-50 MPC, Elevation 734-1.78 MPC.

This is a Severity Level V Violation (Supplement IV).

1.

Admission or Denial of the Alleged Violation TVA admits the violation occurred as stated.

2.

Reasons for the Violation if Admitted On April 28, 1982, the auxiliary building constant air monitors and radiation monitor RM-14 frisking monitors indicated a slight increase above normal background. Health Physics immediately surveyed and collected air samples throughout the auxiliary building. While the air samples were being analyzed, additional data was collected. The health physics investigation indicated a puff (noncontinual) release of noble gases was emitted from the vent line of the boric acid storage tank.

The noble gases were transported through the auxiliary building by the normal ventilation system. This situation caused the airborne activity to be elusive and the data collected from a previous air sample was invalid by the time the sample was analyzed. Therefore, the total auxiliary building was not posted as an airborne radioactivity area.

l 3

Corrective Steps Which Have Been Taken and the Results Achieved l

The boric acid storage tank ventilation system was temporarily modified to prevent the release of radioactive materials to the auxiliary building atmosphere.

4.

Corrective Steps Which Will Be Taken to Avoid Further Violations The boric acid storage tank ventilation system is currently being reviewed for possible future modifications to prevent inadvertent release of airborne radioactivity to the auxiliary building atmosphere. Health Physics has been instructed to properly zone all affected areas should the situation occur in l

the future.

l l

S.

Date When Full Compliance Will Be Achieved Full compliance of 10 CFR 20.203(d) was achieved on September 1, 1982.

-