__

TENNESSEE VALLEY AUTHORITY CH ATTANOOGA. TENNESSEE 374ol 400 Chestnut Street Tower II March 18, 1983 Director of Nuclear Reactor Regulation Attention: Ms. E. Adensam, Chief Licensing Branch No. 4 Division of Licensing, U.S. Nuclear Regulatory Comission Washington, D.C.

20555

Dear Ms. Adensam:

In the Matter of the

)

Docket Nos. 50-327 Tennessee Valley Authority )

50-328 On March 7,1983, we had a telephone conversation with Carl Stahle of your staff and Don Brinkman, NRC, to discuss the acceptance criteria for the surveillance requirement for the Emergency Gas Treatment System (EGTS) charcoal filters. The NRC agreed that for our Sequoyah Nuclear Plant units 1 and 2, the acceptance criteria for surveillance requirement for the charcoal filters (TS 4.6.1.8) defined by Table 2 of Regulatory Guide 1.52, Revision 2, is less than 1-percent methyl iodine penetration at a relative humidity of 70 percent per test 5.b.

If you have any questions, please get in touch with Jerry Wills at FTS 858-2685.

i Very truly yours TENNESSEE VALLEY AUTHORITY

\\.

L. M. Mills, nager Nuclear Licensing Sworn a d subscr before me d u 1983 th a /

day of Mf

-~A*w 1JAV H

o ai Expires #(

/

cc:

U.S. Nuclear Regulatory Commission Region II

[

Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303 8303220156 830318 PDR ADOCK 05000327 P