f r

x-i

  • 5 T,'

SOUTH CAROLINA ELECTRIC a GAS COMPANY PO$f OF FIC. BOM 764 W

AgouryqA otg4 eerie P

ou T C.NicMots,Jn g

v.c. m.......... o.ou, c oc o.

Ebbruary 15, 1982 gGg.p s

uoca.. o....no.

mag 1982n&

T no

  1. m,/ei$%g A% n

/

V' Mr. James P. O'Reilly, Director Iq J7sg U. S. Nuclear Regulatory Commission

/F /

g Region II, Suite 3100 N

101 Marietta Street, N. W.

Atlanta, Georgia 30303

Subject:

Virgil C. Sunmer Nuclear Station Docket No. 50/395 Substantial Safety Hazard Service Water Pumps Nuclear Eng. File 3.1051

Dear Mr. O'Reilly:

On Ebbruary 8,1982, Mr. Virgil Brownlee of NRC Region II was notified of a reportable substantial safety hazard defined by 10 CER 21 concerning the service water pamp motors. Wis its had previously been reported as a potential significant deficiency or substantial safety hazard on August 19, 1981, and in an interim letter on Septmber 18, 1981. This item is being reported under the provisions of 10 CER 50.55e reprting program of South Carolina Electric and Gas Oxnpany.

We information on the attachment to this letter serves as the final reprt.

If you have any questions, please advise.

Very truly yours, T. C. Nichols, Jr.

WDS:'ICN:glb Attachment cc:

Page Two Sfl amem.cdm 8203080283 820215 PDR ADOCK 05000395 S

PDR

I

(

Mr. James P. O'Reilly Ebbruary 15, 1982 Page Two 4

cc:

V. C. Sunener T. C. Nichols, Jr.

G. H. Fischer H. N. Cyrus H. T. Babb D. A. Natanc.:.

~

M. B. Whitaker, Jr.

W. A. Williams, Jr.

O. S. Bradham R. B. Clary M. N. Browne H. I. Donnelly A. R. Koon H. Radin O. W. Dixon, Jr.

Site QA C. L. Ligon (NSRC)

G. J. Braddick J. L. Skolds J. B. Knotts, Jr.

B. A. Bursey J. C. Ruoff I&E (Washington)

Docunent Management Branch (55e, 21, LER only)

NICF File L

f 10CER21 - SUBSTANTIAL SAFETY HAZARD 1.

Name and Address of Reporting Individual Wayne D. Stuart South Carolina Electric and Gas Q:rnpany P. O. Box 764 Columbia, South Carolina 29218 2.

Identification of Basic Canponent Service Water Pump Motors MPP-39A-Si MPP-39B-Si MPP-39C-Si 3.

Identification of Firm Supplying Canponent Westinghouse Electric Corporation 4.

Nature of Defect, Substantial Safety Hazard Created, and Evaluation The absence of a factory installed vent in the upper bearing pot of the Service Water Pump Motors creatal a siphoning effect on the bearing oil pot. The siphonirs effect created a potential for fire as oil was drawn fran the oil reservoir to the motor exterior. The condition is attributable to all three Service Water Pump Fbtors.

The Service Water Systan is essential to the safe operation and shutdown of the nuclear plant. Loss of one or trore Service Water Pump Motors due tn fire could result in a loss of the Service Water Systan.

5.

Date Information of Defect Was Obtained August 3, 1981 6.

Number and Location of Defect Service Water Pung House MPP-39A-SW MPP-39B-Si MPP-39C-SW

~

e 4

7.

Corrective Action Westinghouse was contactal by South Carolina Electric and Gas Chnpany and proposed drilling a vent hole in the top of the Service Water Motor bearing pot to eliminate the oil siphoning. 'Ihe vent has been installed and the siphoning and attendant oil leakage has been corrected.

8.

Advice to Purchas=_r or Licensee Inspect mobe for installation of upper bearing pot vent.